Standard Method of Test for
Slump of Hydraulic
Cement Concrete
AASHTO Designation: T 119M/T 119-13
ASTM Designation: C143/C143M-12
American Association of State Highway and Transportation Officials
444 North Capitol Street N.W., Suite 249
Washington, D.C. 20001
© 2015 by the American Association of State Highway and Transportation Officials.
All rights reserved. Duplication is a violation of applicable law.
TS-3b T 119M/T 119-1 AASHTO
Standard Method of Test for
Slump of Hydraulic Cement Concrete
AASHTO Designation: T 119M/T 119-13
ASTM Designation: C143/C143M-12
1. SCOPE
1.1. This test method covers determination of slump of concrete, both in the laboratory and in the field.
1.2. The values stated in either SI units or inch-pound units are to be regarded separately as standard.
Within the text, the inch-pound units are shown in brackets. The values stated in each system are
not exact equivalents; therefore, each system shall be used independently of the other. Combining
values from the two systems may result in nonconformance with the standard.
1.3. The text of the standard reference notes and footnotes provide explanatory material. These notes
and footnotes (excluding those in tables and figures) shall not be considered as requirements of the
standard.
1.4. This standard does not purport to address all of the safety concerns associated with its use. It is
the responsibility of the user of this standard to establish appropriate safety and health practices
and determine the applicability of regulatory limitations prior to use.
WarningFresh hydraulic cementitious mixtures are caustic and may cause chemical burns to
skin and tissue upon prolonged exposure.
2. REFERENCED DOCUMENTS
2.1. AASHTO Standards:
R 60, Sampling Freshly Mixed Concrete
T 23, Making and Curing Concrete Test Specimens in the Field
T 121M/T 121, Density (Unit Weight), Yield, and Air Content (Gravimetric) of Concrete
T 152, Air Content of Freshly Mixed Concrete by the Pressure Method
T 196M/T 196, Air Content of Freshly Mixed Concrete by the Volumetric Method
2.2. ASTM Standards:
C150/C150M, Standard Specification for Portland Cement
C670, Standard Practice for Preparing Precision and Bias Statements for Test Methods for
Construction Materials
3. SUMMARY OF TEST METHOD
3.1. A sample of freshly mixed concrete is placed and compacted by rodding in a mold shaped as the
frustum of a cone. The mold is raised and the concrete allowed to subside. The vertical distance
between the original and the displaced position of the center of the top surface of the concrete is
measured and reported as the slump of the concrete.
© 2015 by the American Association of State Highway and Transportation Officials.
All rights reserved. Duplication is a violation of applicable law.
TS-3b T 119M/T 119-2 AASHTO
4. SIGNIFICANCE AND USE
4.1. This test method is intended to provide the user with a procedure to determine the slump of plastic
hydraulic cement concretes.
Note 1This test method was originally developed to provide a technique to monitor the
consistency of unhardened concrete. Under laboratory conditions, with strict control of all
concrete materials, the slump is generally found to increase proportionally with the water content
of a given concrete mixture and thus to be inversely related to concrete strength. Under field
conditions, however, such a strength relationship is not clearly and consistently shown. Care
should therefore be taken in relating slump results obtained under field conditions to strength.
4.2. This test method is considered applicable to plastic concrete having coarse aggregate up to
37.5 mm [1.5 in.]. If the coarse aggregate is larger than 37.5 mm [1.5 in.] in size, the test method
is applicable when it is performed on the fraction of concrete passing a 37.5-mm [1.5-in.] sieve,
with the larger aggregate being removed in accordance with the section titled “Additional
Procedures for Large Maximum Size Aggregate Concrete” in R 60.
4.3. This test method is not considered applicable to nonplastic and noncohesive concrete.
Note 2Concretes having slumps less than 15 mm [0.5 in.] may not be adequately plastic and
concretes having slumps greater than about 230 mm [9 in.] may not be adequately cohesive for
this test to have significance. Caution should be exercised in interpreting such results.
5. APPARATUS
5.1. MoldThe test specimen shall be formed in a mold made of metal not readily attacked by the
cement paste. The metal shall not be thinner than 1.5 mm [0.060 in.] and, if formed by the
spinning process, there shall be no point on the mold at which the thickness is less than 1.15 mm
[0.045 in.]. The mold shall be in the form of the lateral surface of the frustum of a cone with the
base 203 mm [8 in.] in diameter, the top 102 mm [4 in.] in diameter, and the height 305 mm
[12 in.]. Individual diameters and heights shall be within ±3.2 mm [0.125 in.] of the prescribed
dimensions. The base and the top shall be open and parallel to each other and at right angles to the
axis of the cone. The mold shall be provided with foot pieces and handles similar to those shown
in Figure 1. The mold shall be constructed without a seam. The interior of the mold shall be
relatively smooth and free from projections. A mold that clamps to a nonabsorbent base plate is
acceptable instead of the one illustrated, provided the clamping arrangement is such that it can be
fully released without movement of the mold and the base is large enough to contain all of the
slumped concrete in an acceptable test.
5.1.1. Check and record conformance to the mold’s specified dimensions when it is purchased or first
placed in service and at least annually thereafter.
5.1.2. Mold with Alternative Materials:
5.1.2.1. Molds other than metal are permitted if the following requirements are met: The mold shall meet
the shape, height, and internal dimensional requirements of Section 5.1. The mold shall be
sufficiently rigid to maintain the specified dimensions and tolerances during use, resistant to
impact forces, and shall be nonabsorbent. The mold shall be demonstrated to provide test results
comparable to those obtained when using a metal mold meeting the requirements of Section 5.1.
Comparability shall be demonstrated on behalf of the manufacturer by an independent testing
laboratory. Test for comparability shall consist of not less than 10 consecutive pairs of
comparisons performed at each of three different slumps ranging from 50 to 200 mm [2 to 8 in.].
No individual test results shall vary by more than 15 mm [0.50 in.] from that obtained using the
metal mold. The average test results of each slump range obtained using the mold constructed of
alternative material shall not vary by more than 6 mm [0.25 in.] from the average of test results
© 2015 by the American Association of State Highway and Transportation Officials.
All rights reserved. Duplication is a violation of applicable law.
摘要:

This document provides the standard specification for the AASHTO T119M/T119-13 and ASTM C143/C143M-12 test methods, which are used to determine the slump of hydraulic-cement concrete in both laboratory and field conditions. The test measures the vert

展开>> 收起<<