加拿大薄钢板建筑学会 CSSBI S5-2019

VIP专免
小气猫 2024-12-06 12 189KB 7 页 16星币
侵权投诉
CSSBI S5-2019:
Guide Specication for Wind Bearing Steel Studs
Copyright © June 2019 All rights reserved. This publication, nor any part thereof, may be
reproduced in any form without the written permission of the publisher.
SPECIFIER NOTES:
This specication is written on the assumption that structural
design of the framing is the responsibility of the Contractor. It also
assumes that division of the work between subcontractors is the
responsibility of the Contractor alone, and done without reliance
on the specications.
For use as a contract document:
Delete Specier Notes
Choose appropriate selections in square brackets
Delete selections in square brackets that do not apply
Make any other project specic amendments that are
appropriate.
This publication replaces the previous edition dated January 2011.
1. GENERAL
1.1 Description of System
Wind bearing steel studs includes:
.1 Wall studs subjected to lateral loads (no
axial loads other than self-weight and the
weight of applied nishes)
.2 Steel bridging
.3 Top and bottom track
.4 Head, sill and jamb members for wall
openings
.5 Stud, bridging and track connections
.6 Top and bottom connections to the main
structure including detailing to
accommodate oor and/or roof deections.
Specier Note: Non-loadbearing interior partition studs are
outside the scope of this specication. Refer to CSSBI S18
for a non-load bearing stud guide specication.
1.2 Related Work
Specier Note: In the applicable related sections, reference
this section for the specication of wind bearing steel studs.
.1 Section [ 01___ ] Allowances for independent
inspection or testing.
.2 Section [ 03___ ] Concrete
.3 Section [ 04___ ] Masonry
Specier Note: Reference the section where masonry ties
connecting to steel studs are specied.
.4 Section [ 06___ ] Wood sheathing
.5 Section [ 07___ ] Insulation
Specier Note: Reference the section(s) where insulation in
the stud space and exterior insulation are specied.
.6 Section [ ____ ] [ _________________ ]
Specier Note: List section(s) where other exterior cladding
or nishes attached to the wind bearing studs are specied.
.7 Section [ 07___ ] Air barriers and/or vapour
retarders
.8 Section [ 08___ ] Doors and windows
.9 Section [ 09___ ] Non load-bearing wall
framing systems
.10 Section [ 09___ ] Gypsum board
Specier Note: Reference the section(s) where gypsum
board nish attached to framing and exterior gypsum
sheathing is specied. If the gypsum board/sheathing is to
function as an air barrier, ensure that screw spacing, board
thickness, and orientation required by wind loads have been
covered there.
.11 Section [ _____ ] [ __________________ ]
1.3 References
Where referenced standards conict with this
specication, this specication governs.
Referenced standards refer to the latest edition.
Specier Note: As an alternative to specifying the “latest
edition”, add current dates to the standards listed below.
.1 National Building Code of Canada
.2 [Ontario] [ _____ ] Building Code
Canadian Sheet Steel Building Institute June 2019
652 Bishop St. N., Unit 2A, Cambridge, Ontario, Canada N3H 4V6 · Telephone (519) 650-1285 · Fax (519) 650-8081 · www.cssbi.ca
Canadian Sheet Steel Building Institute June 2019
652 Bishop St. N., Unit 2A, Cambridge, Ontario, Canada N3H 4V6 · Telephone (519) 650-1285 · Fax (519) 650-8081 · www.cssbi.ca
2
.3 [CAN/CSA-S16 Design of Steel Structures]
.4 [CSA-S136 North American Specication for
the Design of Cold-Formed Steel Structural
Members]
.5 [CSA W47.1 Certication of Companies for
Fusion Welding of Steel]
.6 [CSA W59 Welded Steel Construction]
.7 [ANSI/AWS D1.3 Structural Welding Code –
Sheet Steel]
.8 [CSA A370 Connectors for Masonry]
.9 [CSA S304.1 Design of Masonry
Structures]
.10 [ASTM A307 Standard Specication for
Carbon Steel Bolts and Studs, 60000 PSI
Tensile Strength]
.11 [ASTM F3125M, Standard Specication
for High Strength Structural Bolts, Steel
and Alloy Steel, Heat Treated, 120 ksi
(830 MPa) and 150 ksi (1040 MPa) Minimum
Tensile Strength, Inch and Metric
Dimensions]
.12 [ASTM A653/A653M Standard Specication
for Steel Sheet Zinc-Coated (Galvanized)
or Zinc-Iron Alloy Coated (Galvannealed) by
the Hot-Dip Process]
.13 [ASTM A792/A792M Standard Specication
for Steel Sheet, 55% Aluminum-Zinc Alloy-
Coated by the Hot-Dip Process]
.14 [CAN/CGSB-1.181 Ready-Mixed Organic
Zinc-Rich Coating]
.15 [CAN/ULC-S101 Standard Methods of Fire
Endurance Tests of Building Construction
and Materials]
.16 [CSSBI-61 Manufacturer Certication
Requirements for Cold Formed Steel
Framing Members]
.17 [AISI S240 North American Standard for
Cold-Formed Steel Structural Framing]
.18 [ ________ ]
Specier Note: List standards referenced elsewhere in this
specication.
1.4 Quality Assurance
Retain a Professional Engineer registered in [Canada]
[the province of __________ ] to design the wind
bearing steel stud wall system; to prepare, seal
and sign all shop drawings; and to perform eld
review. Shop drawings shall show both design and
installation requirements.
1.5 Design Criteria
.1 Design shall be based on Limit States
Design principles using factored loads and
resistances.
.2 Loads and load factors shall be in
accordance with the National Building
Code of Canada. For wind load calculations,
the reference velocity pressure, q, shall be
based on a 1 in 50 probability of being
exceeded in any one year.
.3 Resistances and resistance factors shall be
determined in accordance with the National
Building Code of Canada and CSA-S136.
.4 Conform to the requirements of re
rated assemblies [specied] [ which have
been tested in accordance with CAN/
ULC-S101 and provide a re resistance
rating of [ ___________ ] ].
.5 Stud depths are shown on the drawings.
Adjust stud material thicknesses and
spacings, as required by the design criteria.
Use greater or lesser stud and joist depths
only if approved by the [Project Engineer]
[Architect].
Specier Note: Note that maximum spacings (Section 1.5.6)
and minimum design thicknesses (Section 1.5.7) must also
be considered. In addition, to avoid contractual confusion:
Do not show stud and joist thicknesses or spacings on
the Architectural or Structural drawings
Do not use gauge as a thickness designation.
.6 Space wall studs at [305] [406] [610]
[ ____ ] mm maximum. Use lesser stud
spacings if required by the design criteria.
Specier Note: The structural performance of the collateral
facing materials such as gypsum drywall, plywood or OSB
and their associated performance as air barriers, vapour
retarders, etc. will also limit the spacing of supporting
members.
.7 For studs, conform to the design
thicknesses in Table 1. Use greater stud
thicknesses if required by the design criteria.
Canadian Sheet Steel Building Institute June 2019
652 Bishop St. N., Unit 2A, Cambridge, Ontario, Canada N3H 4V6 · Telephone (519) 650-1285 · Fax (519) 650-8081 · www.cssbi.ca
3
Table 1: Minimum Thicknesses
Stud Depth
(mm)
Minimum Base
Steel Thickness
Exclusive of
Coating (mm)
Design Thick-
ness Exclusive
of Coating (mm)
92 0.836 0.879
102 0.836 0.879
152 0.836 0.879
203 1.087 1.146
Specier Note: The minimum base steel thicknesses in
Table 1 are 95% of the design thickness as limited by
CSA-S136
[For wall studs supporting brick veneer, the minimum
thickness exclusive of coating shall be the greater
of the minimum thicknesses in Table 1 or [1.087 mm]
[ _____ ] ].
Specier Note: The minimum design thicknesses in Table 1
satisfy the requirement in S136 for web height to thickness
ratio not greater than 200 assuming an inside bend radius
of 2t.
.8 The minimum thickness for bridging channel
shall be 1.087 mm. Use greater bridging
channel design thickness if required by the
design criteria.
.9 The minimum thickness for clip angles shall
be 1.367 mm. Use greater clip angle
thickness if required by the design criteria.
.10 Maximum exural deections under
specied wind loads shall conform to the
following:
.1 Wall studs supporting masonry veneer
shall meet the requirements of CSA
S304.1 with stud deections limited to
L/360.
Specier Note: The deection and spacing of steel
studs supporting masonry veneer is controlled by the
requirements of the masonry design standard, CSA S304.1.
.2 Wall studs supporting other nishes,
L/360.
.11 Design connections to accommodate
vertical deection movement of the
structure, frame shortening and vertical
tolerances without imposing axial loads
onto the framing. Leave a minimum gap
of [12 mm] [ ____ ]. Larger gaps may be
required to accommodate structural
movement. Co-ordinate with the Project
Structural Engineer.
.12 Limit free play in connections perpendicular
to the plane of the framing to ± [0.5]
[ ____ ] mm relative to the building structure.
Specier Note: Free play does not include the deection
under applied load. The provisions in 1.5.12 do not apply to
masonry ties covered by CSA-A370.
.13 Design components and assemblies
to accommodate specied erection
tolerances of the structure.
.14 Design bridging to prevent member rotation
and member translation perpendicular to
the minor axis. Provide for secondary stress
eects due to torsion between lines of
bridging. [Collateral sheathing may be
used to help restrain member rotation and
translation perpendicular to the minor
axis]. [Do not rely on collateral sheathing to
help restrain member rotation and translation
perpendicular to the minor axis]. Provide
bridging at 1524 mm o.c. maximum.
Space bridging at equal intervals over
the span length of the member. Closer
spacings may be required to satisfy
structural requirements.
Specier Note: Some sheathing materials such as gypsum
drywall may lose their structural integrity when subject to a
moist environment or when subjected to a sucient number
of load cycles. Such materials are generally not suitable
to act as structural bracing. If the sheathing is utilized
for bracing, it is standard practice in the industry to also
provide sucient steel bridging to align members during
erection and to provide the necessary structural integrity
during construction as well as in the completed structure.
.15 Design anchorage and splice details for
bridging.
.16 Design for local loading due to anchorage of
cladding and interior wall mounted xtures
where shown.
.17 Connections between wind bearing steel
stud members shall be by bolts, welding or
sheet metal screws.
.18 Provide head, sill and jamb members and
connections to frame openings larger than
[100] [ ____ ] mm in any dimension.

标签: #钢 #薄钢板 #钢板

摘要:

CSSBI S5-2019是由加拿大薄钢板建筑学会发布的权威标准规范,专门针对薄钢板在建筑结构中的应用提供技术指南与性能要求。该标准覆盖了冷弯薄壁型钢的设计、制造、安装及质量控制等关键环节,适用于住宅、商业及工业建筑项目,旨在确保建筑结构的强度、耐久性与安全性。对于工程师、建筑师、承包商及相关从业者而言,掌握CSSBI S5-2019有助于提升项目合规性,优化材料选用与施工流程,并降低结构失效风险。该文件是加拿大建筑行业推行薄钢板标准化应用的重要参考,尤其适合从事绿色建筑、轻型钢结构或抗震设计领

展开>> 收起<<
加拿大薄钢板建筑学会 CSSBI S5-2019.pdf

共7页,预览4页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:小气猫 分类:国际标准 价格:16星币 属性:7 页 大小:189KB 格式:PDF 时间:2024-12-06

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 7
客服
关注