Designation: C739 −24
Standard Specification for
Cellulosic Fiber Loose-Fill Thermal Insulation
1
This standard is issued under the fixed designation C739; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This specification covers the composition and physical
requirements of chemically treated, recycled cellulosic fiber
loose-fill type thermal insulation for use in attics or enclosed
spaces in housing, and other framed buildings within the
ambient temperature range from −45 to 90°C by pneumatic or
pouring application. While products that comply with this
specification are used in various constructions, they are adapt-
able primarily, but not exclusively, to wood joist, rafters, and
stud construction.
1.2 The values stated in SI units are to be regarded as
standard. No other units of measurement are included in this
standard.
1.3 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
priate safety, health, and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
1.4 This international standard was developed in accor-
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
2
B152/B152M Specification for Copper Sheet, Strip, Plate,
and Rolled Bar
C168 Terminology Relating to Thermal Insulation
C177 Test Method for Steady-State Heat Flux Measure-
ments and Thermal Transmission Properties by Means of
the Guarded-Hot-Plate Apparatus
C518 Test Method for Steady-State Thermal Transmission
Properties by Means of the Heat Flow Meter Apparatus
C687 Practice for Determination of Thermal Resistance of
Loose-Fill Building Insulation
C1114 Test Method for Steady-State Thermal Transmission
Properties by Means of the Thin-Heater Apparatus
C1338 Test Method for Determining Fungi Resistance of
Insulation Materials and Facings
C1363 Test Method for Thermal Performance of Building
Materials and Envelope Assemblies by Means of a Hot
Box Apparatus
C1374 Test Method for Determination of Installed Thick-
ness of Pneumatically Applied Loose-Fill Building Insu-
lation
C1485 Test Method for Critical Radiant Flux of Exposed
Attic Floor Insulation Using an Electric Radiant Heat
Energy Source
C1630 Guide for Development of Coverage Charts for
Loose-Fill Thermal Building Insulations
E177 Practice for Use of the Terms Precision and Bias in
ASTM Test Methods
E691 Practice for Conducting an Interlaboratory Study to
Determine the Precision of a Test Method
E970 Test Method for Critical Radiant Flux of Exposed Attic
Floor Insulation Using a Radiant Heat Energy Source
3. Terminology
3.1 Definitions—For definitions of terms used in this
specification, see Terminology C168.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 attic—an enclosed space between the roof and ceiling
of the occupied part of a building.
3.2.2 critical radiant flux—the level of incident radiant heat
energy on the attic floor insulation system at the most distant
flame-out point (W/cm
2
).
4. Materials and Manufacture
4.1 The basic material shall be recycled cellulosic fiber
made from selected paper, paperboard stock, or ground wood
stock, excluding contaminated materials, which may reason-
ably be expected to be retained in the finished product. Suitable
1
This specification is under the jurisdiction of ASTM Committee C16 on
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on
Blanket and Loose Fill Insulation.
Current edition approved March 1, 2024. Published March 2024. Originally
approved in 1973. Last previous edition approved in 2021 as C739 – 21a. DOI:
10.1520/C0739-24.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
1
chemicals are introduced to provide properties such as flame
resistance, processing, and handling characteristics.
4.2 The basic material may be processed into a form
suitable for installation by pneumatic or pouring methods.
5. Physical and Chemical Properties
5.1 Design Density—The design density shall be determined
in accordance with Section 8. Report all units in kg/m
3
.
5.1.1 Design density is not a basis for acceptance or
rejection.
5.2 Corrosiveness—The loose-fill insulation material shall
be tested for corrosiveness as specified in Section 9. The
composition of the insulation material shall be such that after
testing, no perforation of the 3-mil (76-µm) metal specimens
shall be evident when the specimens are observed over a 40-W
appliance light bulb. Notches extending into the coupon 3 mm
or less from any edge shall be ignored.
5.3 Critical Radiant Flux—When tested in accordance with
Section 10, the critical radiant flux shall be ≥0.12 W/cm
2
. All
values shall be reported to two significant digits.
5.4 Fungi Resistance—The loose-fill insulation material
shall be tested and shall pass fungi resistance as specified in
Section 11. If the growth on two or more of the replicate test
items is greater than that on the comparative item, the test item
shall be considered to fail.
NOTE 1—If the manufacturing claims the insulation kills or controls
insects or rodents, or both, the product must be registered as a pesticide
under the Federal Insecticide, Fungicide and Rodentic Act, as amended,
and must also be registered in accordance with state pesticide statutes.
5.5 Moisture Vapor Sorption—Moisture gain in the insula-
tion shall be no more than 15 % by weight when tested in
accordance with Section 12.
5.6 Odor Emission—Any sample producing a detectable
odor that is classified as objectionable and strong or very strong
by more than two panel members shall be considered to have
failed the test when tested in accordance with Section 13.
5.7 Smoldering Combustion—When tested in accordance
with the smoldering combustion test method in Section 14, the
insulation shall show no evidence of flaming and a weight loss
no greater than 15 %.
5.8 Thermal Resistance—The standard thermal resistance
values normally recommended for open application are: 2.3,
3.4., 3.9, 5.3, 6.7, and 8.6 and are expressed in K·m
2
/W. The
thermal resistance Rfor the average of any (four) randomly
selected specimens shall not be more than 5 % below the listed
Rvalue when tested in accordance with Section 15.Rvalues
other than those listed shall be as agreed upon between the
supplier and the purchaser.
6. Workmanship, Finish, and Appearance
6.1 The product shall be free of extraneous foreign materials
such as metals and glass that will adversely affect the perfor-
mance in service.
TEST METHODS
7. Summary
7.1 The following tests shall be conducted on loose-fill
cellulosic insulation at the measured design density: moisture
vapor sorption, smoldering combustion, and thermal resis-
tance.
NOTE 2—The importance of an insulation’s product to maintain its fire
retardant characteristics is recognized. A task group in ASTM C16.31 is
currently studying methods to ascertain if there is a long-term deteriora-
tion of fire performance characteristics of cellulose insulation. Should the
need for a permanency test be determined by this task group and a test
method be developed and finalized, it will become a part of this
specification.
8. Design Density
8.1 Scope—This test method provides a basis for calculating
the product coverage values and for conducting physical
property tests requiring the use of design density for sample
preparation.
8.2 Significance and Use—The design density is the ap-
proximate density expected after long-term attic application.
8.3 Apparatus and Materials:
8.3.1 Insulation Specimen Container—A beaker having a
flat bottom and an inside diameter of 15.0 61 cm, straight
sides. The height of the beaker shall be such that the distance
between the bottom of the cyclone and the top edge of the
beaker is 8.50 61.0 cm.
8.3.2 Flat Rigid Disk, having a total weight of 75 65 g and
of a suitable diameter to fit loosely into the specimen container.
Weight may be added to the center of the disk to bring the total
weight to the required 75 65 g.
8.3.3 Balance, having a 2-kg capacity accurate to 60.2 g.
8.3.4 Blower Apparatus, having two blower units (supply
and overflow) meeting the following specifications:
8.3.4.1 Each blower apparatus shall be capable of blowing
an average of 272.2 kg of insulation per hour.
8.3.4.2 Each blower apparatus shall have a nominal air flow
velocity of 0.38 m/s.
8.3.4.3 Each blower apparatus shall have a nominal motor
speed of 16 450 r/min at 115 V (a-c).
8.3.5 Shaker Unit, having a capability of shaking 4.5 kg of
weight with a vertical motion of 0.5 g rms acceleration at an
approximate frequency of 9 Hz and displacement of approxi-
mately 1.17 60.08 cm.
8.3.6 Fill Chamber, having inside dimensions of 45.7 cm
high by 38.1 cm wide by 38.1 cm deep, with covered openings
that will allow a radiant panel tray to be slid through the
chamber (see Fig. 1).
8.3.7 Cyclone Receiver—See Fig. 2.
8.3.8 Hose—Various lengths of nominal 5.08-cm diameter
hose (see Fig. 1):
8.3.8.1 Supply Source Hose, 274.3 65.1 cm.
8.3.8.2 Cyclone Receiver Hose, 182.9 65.1 cm.
8.3.8.3 Fill Chamber Exit Hose, 91.4 65.1 cm.
8.3.8.4 Overflow Exhaust Hose, length as needed.
8.3.9 Blower Controls, having capability of operating the
two blowers at 40 V rms and 12 A.
C739 − 24
2
8.3.10 Insulation Holding Container, capable of holding
four times the amount of insulation required to fill the
specimen container.
8.3.11 Garden Rake, with steel teeth.
8.4 Conditioning:
8.4.1 Condition specimens to equilibrium at 21 62.0°C and
50 65 % relative humidity in an open top mesh bottom
container not exceeding 10.16 cm in depth and position in such
a way to allow free movement of air on exposed sides. A
change in net weight of the specimen that is less than 1 % in
two consecutive weighings with 24 h between each weighing
constitutes equilibrium.
8.4.2 If ambient laboratory conditions are different from the
conditioning requirements specified in 8.4.1, begin testing the
specimen for design density within 10 min after it has been
removed from the conditioned area.
8.5 Procedure for Pneumatic Applications:
8.5.1 Conduct the test in an area conditioned in accordance
with 8.4.1.
8.5.2 Blow the material through a commercial blower using
30.48 m of 5.08 cm hose into a sample receiver while holding
the hose horizontally at a height of four feet.
8.5.3 Set up the apparatus as shown in Fig. 1. Connect one
end of the supply source hose to the intake of the supply
blower. Use the other end of the supply source hose to pick up
insulation from the holding container. Connect one end of the
cyclone receiver hose to the outlet of the supply blower and the
other end to the fill chamber. Place the fill chamber on a flat
and level surface. Connect one end of the variable length
overflow exhaust hose to the outlet of the overflow blower.
Conveniently place the other end to reduce insulation dust in
the test area.
8.5.4 Weigh the empty insulation specimen container and
record its weight.
8.5.5 Place the empty insulation specimen container in the
fill chamber, centered under the cyclone receiver, and close the
front cover.
8.5.6 Adjust the blower control(s) so that the supply and
overflow blowers will operate at a no-load voltage of 40 V rms.
FIG. 1 Partial Insulation Preparation Apparatus
FIG. 2 Cyclone Receiver Weldment
C739 − 24
3
摘要:

ASTM C739-2024 Standard Specification for Cellulosic Fiber Loose-Fill Thermal Insulation 纤维素纤维(木基)的疏松填充绝热材料

展开>> 收起<<
ASTM C739-24 纤维素纤维(木基)的疏松填充绝热材料.pdf

共10页,预览4页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:Carl 分类:国外协会 价格:16星币 属性:10 页 大小:369.2KB 格式:PDF 时间:2024-09-03

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 10
客服
关注