
The 2019 edition of the Automatic Sprinkler Systems Handbook contains the complete mandatory text of the 2019 edition
of NFPA 13, Standard for the Installation of Sprinkler Systems, as well as expert commentary to assist users in their under-
standing and application of the standard. In addition to the commentary text, this edition of the handbook also oers a
number of helpful features, which are described below.
2019 Automatic Sprinkler Systems Handbook
684 Chapter 20 • General Requirements for Storage
for Test for Surface Burning Characteristics of Building Materials, extended for an addi-
tional 20 minutes in the form in which they are installed in the space.
(5) Concealed spaces in which the exposed materials are constructed entirely of fire retar-
dant–treated wood as defined by NFPA 703.
(6) Concealed spaces over isolated small compartments not exceeding 55 ft2 (5.1 m2) in area.
(7) Vertical pipe chases under 10 ft2 (0.9 m2), provided that in multifloor buildings the chases
are firestopped at each floor using materials equivalent to the floor construction. Such
pipe chases shall contain no sources of ignition, piping shall be noncombustible, and pipe
penetrations at each floor shall be properly sealed.
(8) Exterior columns under 10 ft2 (0.9 m2) in area formed by studs or wood joists, supporting
exterior canopies that are fully protected with a sprinkler system.
(9) Cavities within unsprinklered wall spaces.
Subsection 20.7.2 lists nine types of concealed spaces that are not required to address the increase in
the design area because the lack of combustibility in the construction of the concealed space limits the
probability that a fire will move through the concealed space. In those cases, the existence of combustible
materials, such as telephone/computer wire, drain pipes, or other materials, is typically not a sufficient
concern to require additional sprinkler protection.
CLOSER LOOK [20.7]
Unsprinklered Combustible Concealed Spaces
In an ordinary hazard occupancy with a 60-minute water supply
duration requirement and having an unsprinklered combustible
concealed space between the first and second floors, the applica-
tion of the 3000 ft2 (280 m2) design area is required. In this case, the
design area for the sprinkler system on both the first and second
floors would be required to be 3000 ft2 (280 m2) as provided by
20.7.1.1, unless the floor slab completely separates the concealed
space and the second floor has a 1-hour fire resistance rating as
provided by 20.7.1.2. If the building were four stories in height,
the existence of the unsprinklered combustible concealed space
between the first and second floors would not affect the design
area required on the third and fourth floors of the building.
If the drop ceiling below the floor slab that creates the con-
cealed space is necessary for the 1-hour rating of the floor/ceiling
assembly, the design area would apply to the system on the second
floor, because the entire fire-resistive assembly (from the bottom
of the suspended ceiling to the top of the floor slab) would not be
between the concealed space and the area protected by the sec-
ond floor sprinkler system.
The 3000 ft2 (280 m2) design area is intended to be applied
after all the other adjustments required by the density/area method
of calculation, which means that users should pick their points
wisely from the density/area curves. By sliding up the curves to pick
the initial point, users can conserve water and make the system
design more efficient.
The 3000 ft2 (280 m2) design area applies only to sprinklers
using the density/area method, so it does not apply to CMSA and
ESFR sprinkler systems. Because CMSA and ESFR sprinklers are
specifically designed to deal with fires in storage and warehouse
occupancies, it is highly unlikely that a fire would be controlled
or suppressed by such sprinklers and still have sufficient force to
move through a combustible concealed space. Even if a fire did
move through such a concealed space, it is assumed that there are
sufficient safety factors in the design area to deal with additional
sprinklers that might open.
If 9.2.1 does not specifically allow sprinklers to be omitted
from a concealed space, then Section 20.7 cannot be used to jus-
tify omitting sprinklers from those concealed spaces. The design
area cannot be increased to 3000 ft2 (280 m2) while sprinklers are
omitted from a concealed space that is not addressed by 9.2.1.
20.8 Room Design Method .
20.8.1* The water supply requirements for sprinklers only shall be based upon the room that
creates the greatest demand.
A.20.8.1 This subsection allows for calculation of the sprinklers in the largest room, so long
as the calculation produces the greatest hydraulic demand among selection of rooms and
BK-NFPA-13HB19-180218-Chp20.indd 684 10/10/18 9:11 PM
2019 Automatic Sprinkler Systems Handbook
506 Chapter 17 • Installation Requirements for Hanging and Support of System Piping
Slots in the angle iron are a common way to attach the hangers to the angle iron trapeze member. This
allows for flexibility in working with the structure and nominal variations that could exist. However, remov-
ing material from the angle iron to create the slot will reduce the load capacity of the member. These
guidelines are provided to restrict the size and number of slots in an angle iron.
17.4 * Installation of Pipe Hangers .
A.17.4 To enhance permanence, proper hanger installation is important. Installation
procedures should meet industry standards of practice and craftsmanship. For example,
hanger assemblies are straight, perpendicular to the pipe, uniformly located, and snug to the
structure with fasteners fully engaged.
17.4.1 General.
17.4.1.1 Ceiling Sheathing.
17.4.1.1.1* Unless the requirements of 17.4.1.1.2 are met, sprinkler piping shall be supported
independently of the ceiling sheathing.
A.17.4.1.1.1 Fasteners used to support sprinkler system piping should not be attached to ceil-
ings of gypsum or other similar soft material.
17.4.1.1.2 Toggle hangers shall be permitted only for the support of pipe 1½ in. (40 mm) or
smaller in size under ceilings of hollow tile or metal lath and plaster.
FAQ [17.4.1.1.2]
Are toggle hangers permitted to
be utilized in gypsum wallboard
ceilings?
Toggle hangers are not permitted
for use with gypsum wallboard
or other less substantial types of
ceiling materials.
DESIGNER’S CORNER 17.3
Should the hangers supporting the 3 in. (80 mm) Schedule
40 steel pipe trapeze member shown in the illustration
be sized to support the 3 in. (80 mm) Schedule 40 trapeze
member or the 6 in. (150 mm) Schedule 10 sprinkler main?
If the “cookbook” approach to using trapeze hangers as laid out in
Section 17.3 is used, the hangers supporting the trapeze member
should be individually sized to support the 6 in. (150 mm) sprinkler
main. Since the hanger components will not be physically attached
to the 6 in. (150 mm) pipe, a component is needed from a hanger
manufacturer to connect to the 3 in. (80 mm) trapeze member that
will support the load of the 6 in. (150 mm) (water-filled) main. Man-
ufacturers are aware of this requirement and make correct connec-
tions for these situations.
Confusion on this issue stems from previous editions of NFPA
13, in which the rules were not so clear. With a lack of guidance
from NFPA 13 on the subject, many designers and installers would
use hangers sufficient to support the load of the 3 in. (80 mm)
trapeze member in the example. Since there were two such
hangers for each trapeze member, they calculated that the total
capacity of the trapeze would still be sufficient to carry the load
of the sprinkler main, but this was done as an extension of the
building requirements for only the weight of the system piping
plus 250 lb (115 kg). When the sprinkler main is much closer to
one of the trapeze supports than to the other, the two hangers for
the trapeze member might not be able to support the load of the
sprinkler main if they are sized for sharing the load between the
two supports of the trapeze.
To fix this situation, the Technical Committee on Hanging
and Bracing changed the rules in the 2007 edition to require that
the hangers for the trapeze be sized individually to support the
sprinkler main. This approach is the most conservative and will
work for all circumstances, as long as connections to the trapeze
member will support the greater load, which they now do.
Under the performance-based option of 17.1.2, professional
engineers could still design a trapeze with hangers that are
sized to support only the trapeze member if they perform
the calculations to prove that the hanger assembly provides
adequate support overall to the sprinkler main. This calculation
would not be difficult for a structural engineer and would still
comply with NFPA 13.
3 in. trapeze member
6 in. sprinkler main
Hangers in question
Schedule 40 Trapeze Hanger.
BK-NFPA-13HB19-180218-Chp17.indd 506 30/10/18 11:46 AM
➤
Closer Look features provide
further information on selected
topics from the standard.
➤
Designer’s Corner features
provide insight into sprinkler
system design and installation.
➤
Nonmandatory Annex A material
follows its corresponding
mandatory text in the standard.
Automatic Sprinkler Systems Handbook 2019
Section 25.2 • Ceiling-Level Sprinkler Design Criteria in Combination with In-Rack Sprinklers 821
Doors at the lower and intermediate levels and ventilation louvers at the tops of walls were
kept closed during the majority of the fire tests, which minimized the effect of exterior conditions.
The entire test series was fully instrumented with thermocouples attached to rack mem-
bers, simulated building columns, bar joists, and the ceiling.
Racks were constructed of steel vertical and horizontal members designed for 4000 lb
(1815 kg) loads. Vertical members were 8 ft (2.4 m) on center for conventional racks and 4 ft
(1.2 m) on center for simulated automated racks. Racks were 3½ ft (1 m) wide with 6 in. (150 mm)
longitudinal flue space for an overall width of 7½ ft (2.3 m). Simulated automated racks and
slave pallets were used in the main central rack in the 4 ft (1.2 m) aisle tests. Conventional
racks and conventional pallets were used in the main central rack in the 8 ft (2.4 m) aisle tests.
The majority of the tests were conducted with 100 ft2 (9.3 m2) sprinkler spacing.
The test configuration for storage heights of 15 ft (4.6 m), 20 ft (6.1 m), and 25 ft (7.6 m)
covered an 1800 ft2 (167.2 m2) floor area, including aisles between racks. Tests that were used
in producing this standard limited fire damage to this area. The maximum water damage area
anticipated in the standard is 6000 ft2 (555 m2), the upper limit of the design curves.
The test data show that, as density is increased, both the extent of fire damage and sprin-
kler operation are reduced. The data also indicate that, with sprinklers installed in the racks, a
reduction is gained in the area of fire damage and sprinkler operations (e.g., water damage).
Table C.9 illustrates these points. The information shown in the table is taken from the
test series for storage height of 20 ft (6.1 m) using the standard commodity.
Water supply
System control valve
System check valve
Main drain valve
Check valve
Fire department connection
Local waterflow alarm
Feed main to sprinklers
1
2
3
4
5
6
7
8
Sprinkler System Riser Assembly—Equipment Legend
1
2
3
15
11
13
414
5
8
10
8
6
7
13
12
9
Piping (drop) down to in-rack sprinklers
OS&Y control valve
Ceiling/overhead fire sprinklers
In-rack fire sprinkler(s)
Branch line(s)
Rack structure
Roof support structure
11
12
9
10
13
14
15
Sprinkler System & Building—Legend
Note: In-rack sprinkler portion contains more than 20 sprinklers but only occupies portion of area protected by ceiling system.
EXHIBIT 25.3 In-Rack Sprinklers Occupying Only Portion of Area Protected by Ceiling Sprinklers. (Courtesy of Stephan Laforest)
EXHIBIT 25.4 Sectional Control
Valve for In-Rack Sprinklers.
BK-NFPA-13HB19-180218-Chp25.indd 821 17/10/18 12:22 AM
Automatic Sprinkler Systems Handbook 2019
Section 4.5 • System Protection Area Limitations 101
4.5.3 Where single systems protect extra hazard, high-piled storage, or storage covered by
other NFPA standards, and ordinary or light hazard areas, the extra hazard or storage area
coverage shall not exceed the floor area specified for that hazard and the total area coverage
shall not exceed 52,000 ft2 (4830 m2).
4.5.4 The area protected by a single in-rack system includes all of the floor area occupied by
the racks, including aisles, regardless of the number of levels of in-rack sprinklers.
4.5.4.1 Multiple buildings attached by canopies, covered breezeways, common roofs, or a
common wall(s) shall be permitted to be supplied by a single fire sprinkler riser.
4.5.5 The maximum system size shall comply with 4.5.1.
Where acceptable to the local authority having jurisdiction, multiple detached buildings can be protected
with a single sprinkler system. In instances where no water supply is located close by, it would be feasible
to supply the sprinklers in a detached building by extending the sprinkler system from an adjacent build-
ing. In such cases, the best alternative is to extend the water supply and provide the building with its own
sprinkler system. Examples might include portable classrooms, small auxiliary buildings associated with
car dealerships, and similar small adjacent buildings. In such cases, the local authority having jurisdiction
can allow the sprinklers to be supplied by a sprinkler system in an adjacent building. Care should be taken
when the two buildings involved do not have the same ownership or the fire protection is not under the
control of a single party. Such situations can result in impairments that go unknown or delays in accessing
control valves in an emergency situation. Another consideration should be the ability of alarm devices to
identify which areas or buildings are experiencing waterflow. This can be accomplished with visible alarm
annunciation devices such as strobes rather than multiple local alarm bells.
4.5.6* Detached Buildings.
A.4.5.6 Buildings adjacent to a primary structure can be protected by extending the fire sprin-
kler system from the primary structure. This eliminates the need to provide a separate fire
sprinkler system for small auxiliary buildings. Items that should be considered before final-
izing fire sprinkler design should include the following:
(1) Actual physical distance between adjacent structures
(2) Potential for the property to be split into separate parcels and sold separately
(3) Square footage of both the primary and auxiliary structures
(4) Difficulties in providing a separate water supply to the auxiliary structure
(5) Occupancy/hazard of the auxiliary structure
(6) Ability of emergency response personnel to easily identify the structure from which water-
flow is originating
4.5.6.1 Unless the requirements of 4.5.6.2 apply, detached buildings, regardless of separation dis-
tance, that do not meet the criteria of 4.5.4 shall be provided with separate fire sprinkler systems.
4.5.6.2 When acceptable to the authority having jurisdiction, detached structures shall be
permitted to be supplied by the fire sprinkler system of an adjacent building.
N
N
Why would an authority having jurisdiction have concerns about multiple buildings using the same re
sprinkler system?
From the standpoint of an authority having jurisdiction, the primary problem with multiple buildings using
the same sprinkler system occurs if each building is or becomes owned by dierent owners. If the source
building owner stops maintaining the water supply and the buildings are under separate ownership, it be-
comes very dicult to enforce re code maintenance requirements for the dependent building. If the author-
ity having jurisdiction allows the use of the exception in 4.5.6.2, it should be in situations where it is unlikely
or impossible for the ownership of the individual buildings to split or where legal easements are recorded.
ASK THE AHJ
?
Where high-piled storage or
extra hazard occupancies are
mixed with light hazard or
ordinary hazard occupancies, is
it acceptable to exceed 40,000
ft2 (3720 m2) per floor?
A single system that protects
both ordinary or light hazard
areas and solid-piled, palletized,
or rack storage greater than 12 ft
(3.7 m) high or that protects extra
hazard areas can have a coverage
area of up to 52,000 ft2 (4830 m2),
as indicated by 4.5.3. However,
not more than 40,000 ft2 (3720
m2) of that coverage area can be
high-piled storage or hydrauli-
cally designed for extra hazard
occupancies.
The 40,000 ft2 (3720 m2)
maximum extra hazard coverage
area for hydraulically designed
systems is consistent with the
requirements for storage areas
that have similar fire loading. If
the potential exists to use the
ordinary or light hazard areas for
storage in the future, use of the
lower system area of 40,000ft2
(3720 m2) as the allowable
system protection area would be
appropriate.
FAQ [4.5.3]
BK-NFPA-13HB19-180218-Chp04.indd 101 24/10/18 8:25 PM
➤
Detailed exhibits help users
to better visualize equipment,
systems, and concepts.
➤
Shading indicates where text
has changed from the previous
edition of the standard.
➤
Commentary text is colored blue
to distinguish it from the text of
the standard.
FAQs provide detailed answers
to questions commonly asked
of the NFPA 13 staff.
Features of the Automatic Sprinkler
Systems Handbook, 2019 Edition
➤
Nonmandatory Annex C material
follows its corresponding manda-
tory text in the standard.
➤
➤
“N” icons indicate a section,
figure, or table that is new for
this edition of the standard.
➤
Ask the AHJ features provide
insight into questions that
authorities having jurisdiction
often have to answer.
{7d1cf25d-f130-43e0-8b7f-041dc4ddd530}