NFPA 1150-2022 amd1-2022

免费
那山那人那狗 2024-12-29 9 145.43KB 2 页 免费
侵权投诉
Tentative Interim Amendment
NFPA® 1150
Standard on Foam Chemicals for Fires in Class A Fuels
2022 Edition
Reference: 6.2.1, 6.3.1, 6.3.2, 6.3.3(5), 6.4.1, 6.4.2 and 6.4.3(5)
TIA 22-1
(TIA Log #1634)
Pursuant to Section 5 of the NFPA Regulations Governing the Development of NFPA Standards, the National Fire Protection
Association has issued the following Tentative Interim Amendment to NFPA 1150, Standard on Foam Chemicals for Fires
in Class A Fuels, 2022 edition. The TIA was processed by the Technical Committee on Water Additives for Fire Control and
Vapor Mitigation, and was issued by the Standards Council on July 7, 2022, with an effective date of July 27, 2022.
1. Revise paragraph 6.2.1 to read as follows:
6.2.1 The ability of a wetting agent foam solution to extinguish wood crib fires shall be determined with the solution
prepared at the minimum concentration specified for use by the manufacturer. [18:6.2.1]
2. Revise paragraphs 6.3.1 and 6.3.2 and 6.3.3 item (5) to read as follows:
6.3.1 Wetting agent Foam solutions shall extinguish deep-seated cotton fires and exhibit less runoff than water when tested
in accordance with 6.3.2 and 6.3.3. [18:6.3.1]
6.3.2 Tests shall be conducted three times with plain water and three times with the wetting agent foam solution prepared at
the manufacturer’s recommended concentrations. [18:6.3.2]
6.3.3 The tests shall be conducted using a cylindrical basket of perforated sheet steel, 114 mm (4 ½ in.) in diameter and
178 mm (7 in.) high, and ginned cotton weighing 200 g (3.5 oz) shall be used and the test conducted as follows:
(1) …
(5) Pour 250 mL (8.5 fl oz) of test liquid (water or wetting agent foam solution) onto the cotton and catch the runoff in a
pan placed below the basket.
…
[18:6.3.3]
3. Revise paragraphs 6.4.1, 6.4.2 and 6.4.3 item (5) to read as follows:
6.4.1 Wetting agent Foam solutions shall extinguish wood fiberboard fires and exhibit less runoff and weight loss than
water when tested in accordance with 6.4.2 and 6.4.3. [18:6.4.1]
6.4.2 Tests shall be conducted three times with plain water and three times with the wetting agent foam solution prepared at
the manufacturer’s recommended concentrations. [18:6.4.2]
6.4.3 Penetration tests shall be conducted as follows:
(1) …
(5) Spray 250 mL (8.5 fl oz) of test liquid (water or wetting agent foam solution) on the upper surface of the insulation
board using a small sprinkler bottle.
…
[18:6.4.3]
Issue Date: July 7, 2022
Effective Date: July 27, 2022
(Note: For further information on NFPA Codes and Standards, please see www.nfpa.org/docinfo)
Copyright © 2022 All Rights Reserved
NATIONAL FIRE PROTECTION ASSOCIATION
摘要:

NFPA 1150-2022 amd1-2022 是美国消防协会(NFPA)于2022年发布的针对《NFPA 1150-2022 用于A类燃料的泡沫化学品标准》的修订版修正案。该标准文档主要规范了在A类火灾(如木材、纸张、纺织品等普通可燃物)中使用的泡沫灭火化学品的性能、测试方法、环保要求及使用指导。此次修正案(amd1)进一步回应了全球范围内对含氟表面活性剂(如PFAS)的环境与健康关切,明确了低氟或无氟泡沫配方的合规性要求,同时更新了灭火性能测试的评估标准与储存稳定性指标。该文件对于消防设备

展开>> 收起<<
NFPA 1150-2022 amd1-2022.pdf

共2页,预览2页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:那山那人那狗 分类:国外协会 价格:免费 属性:2 页 大小:145.43KB 格式:PDF 时间:2024-12-29

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 2
客服
关注