5.2 Flashover shall be considered to have occurred when
any two of the following conditions have been attained:
(a) Heat release rate exceeds 1 MW.
(b) Heat flux at the floor exceeds 20 kW/m
2
.
(c) Average upper layer temperature exceeds 600 °C.
(d) Flames exit doorway.
(e) A paper target on the floor auto-ignites.
5.2.1 Time to flashover shall be the time from start of test
until the second condition has been attained.
5.3 The potential for the spread of fire to other objects in the
room, remote from the ignition source, is evaluated by mea-
surements of: (a) the total heat flux incident on the center of the
floor, and (b) a characteristic upper level gas temperature in the
room.
5.4 The potential for the spread of fire to objects outside the
room of origin is evaluated by the measurement of the rate of
heat release of the fire.
5.5 Measurements of the rate of production of carbon
monoxide, carbon dioxide, and visible smoke are taken.
5.6 The overall performance of the test specimen is visually
documented by full-color photographic records. Video taping
of the complete fire test is an acceptable alternative to the
photographic record. Such records show when each area of the
test specimen becomes involved in the fire.
5.7 In this procedure, the specimens are subjected to a
specific set of laboratory fire test exposure conditions. If
different test conditions are substituted or the anticipated
end-use conditions are changed, it is not known whether it is
possible by use of this test to predict changes in the perfor-
mance characteristics measured. Therefore, the results are
strictly valid only for the fire test exposure conditions de-
scribed in this procedure.
6. Ignition Source
6.1 The ignition source for the test shall be a gas burner with
a nominal 170 mm by 170 mm (6.7 in. by 6.7 in.) porous top
surface of a refractory material, as shown in Fig. 1.
6.2 The top surface of the burner through which the gas is
supplied shall be located horizontally, 170 mm (6.7 in.) off the
floor, and the burner enclosure shall be in contact with both
walls in a corner of the room opposite from the door, and the
edge of the diffusion surface shall be flush with the wall.
6.3 The burner shall be supplied with C.P. grade propane
(99 % purity), with a net heat of combustion of 46.5 MJ/kg 6
0.5 MJ/kg (20 000 Btu/lb 6200 Btu/lb) The gas flow to the
burner shall be measured with an accuracy of at least 63 %.
The flow measuring equipment shall be calibrated per the
manufacturer’s instructions at least once per year. The heat
output to the burner shall be controlled within 65 % of the
prescribed value.
6.4 The gas supply to the burner shall produce a net heat
output of 100 kW 63 kW (5690 Btu/min 6170 Btu/min) for
the first 10 min, followed by 300 kW 610 kW (17060 Btu/min
6570 Btu/min) for the next 10 min.
NOTE 1—This corresponds to a flow of approximately 67.3 L/min at
100 kW, and 202.0 L/min at 300 kW for propane with a net heat of
combustion of 46.5 MJ/kg, under standard conditions of 101 kPa pressure
and 20 °C temperature.
6.5 The burner shall be ignited by a pilot burner or a
remotely controlled spark igniter.
6.6 Burner controls shall be provided for automatic gas
supply shut-off if flameout occurs.
7. Compartment Geometry and Construction
NOTE 2—The choices for the size of compartment fire experiments are
discussed in Guide E603. The compartment dimensions and tolerances
defined in this section have been chosen to make it convenient to utilize
both standard U.S. size 1.22 m by 2.44 m (4 ft by 8 ft) building materials
or panels and standard 1.2 m by 2.4 m panel sizes common outside the
U.S.
7.1 The room shall consist of four walls at right angles,
floor, and ceiling and shall have the following inner dimen-
sions: 3630 mm 630 mm (12 ft) in length, 2420 mm 620 mm
(8 ft) in width, and 2420 mm 620 mm (8 ft) in height (see Fig.
2). The room shall be placed indoors in an essentially draft
free, conditioned space, large enough to ensure that there is no
influence on the test fire. In order to facilitate the mounting of
the instruments and of the ignition source, it is convenient to
place the test room so that the floor is accessible from beneath.
7.2 There shall be a doorway in the center of one of the
2420 mm by 2420 mm (8 ft by 8 ft) walls, and no other wall,
floor or ceiling openings that allow ventilation. The doorway
shall have the following dimensions: 780 mm 620 mm (30
in.) in width, and 2015 mm 615 mm (80 in.) in height.
7.3 The test compartment shall be a framed or a concrete-
block structure. If the former type of structure is used, the
interior walls and ceiling of the frame shall be lined with
gypsum wallboard or calcium silicate board with a density of
500 kg/m
3
to 800 kg/m
3
(31 lb/ft
3
to 50 lb/ft
3
). The minimum
thickness of the lining material shall be 20 mm (
3
⁄
4
in.).
7.4 If self-supporting panels are tested, a separate exterior
frame or block compartment is not required.
8. Instrumentation in the Fire Room
8.1 The following are minimum requirements for instru-
mentation for this test. Added instrumentation is desirable for
further information.
8.2 Heat Flux:
8.2.1 Specification—The total heat flux meters shall be of
the Gardon (foil) or the Schmidt-Boelter (thermopile) type with
a design range of approximately 50 kW/m
2
(4.4 Btu/ft
2
s). The
target receiving radiation, and possibly to a small extent
convection, shall be flat, circular, not more than 15 mm (
5
⁄
8
in.)
in diameter and coated with a durable matt black finish. The
target shall be contained within a water-cooled body whose
front face shall be of highly polished metal, flat, coinciding
with the plane of the target and circular, with a diameter of not
more than 50 mm (2 in.) The heat flux meter shall have an
accuracy of at least 63 % and a repeatability within 60.5 %.
In operation, the meter shall be maintained at a constant
temperature, at least 5 °C above the dew point.
8.2.2 Location—The heat flux meter shall be mounted at the
geometric center of the floor (see Fig. 2). The target area shall
be between 5 mm and 30 mm (
1
⁄
4
in. and 1
1
⁄
4
in.) above the
floor surface.
E2257 − 24
3