Designation: C411 −19
Standard Test Method for
Hot-Surface Performance of High-Temperature Thermal
Insulation
1
This standard is issued under the fixed designation C411; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This test method covers the determination of the perfor-
mance of commercial sizes of both block and pipe forms of
thermal insulating materials when exposed to simulated hot-
surface application conditions. The term “hot-surface perfor-
mance” has reference to a simulated use-temperature test in
which the heated testing surface is in a horizontal position.
1.2 This test method refers primarily to high-temperature
insulations that are applicable to hot-side temperatures in
excess of 150°F (66°C). It is used for materials such as
preformed insulations, insulating cements, blankets, and the
like, by proper laboratory preparation of the samples.
1.3 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only
and are not considered standard.
1.4 This standard does not purport to address all of the
safety concerns, if any, associated with its use. It is the
responsibility of the user of this standard to establish appro-
priate safety, health, and environmental practices and deter-
mine the applicability of regulatory limitations prior to use.
1.5 This international standard was developed in accor-
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
2
C167 Test Methods for Thickness and Density of Blanket or
Batt Thermal Insulations
C168 Terminology Relating to Thermal Insulation
C356 Test Method for Linear Shrinkage of Preformed High-
Temperature Thermal Insulation Subjected to Soaking
Heat
3. Terminology
3.1 Definitions—Terminology C168 shall apply to the terms
used in this test method.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 sag, n—the extent of thickness loss of pipe insulation,
at the top longitudinal center, due to material fatigue or
decomposition due to elevated temperature.
4. Significance and Use
4.1 Performance in service is the final measure of value for
a thermal insulation, but simulative service tests give useful
indications. One type involves application for a specified time
to a surface heated at a temperature approximately that of
intended service, and noting during the test and afterward,
changes in the material and its properties. Measurement of
these changes are used for predicting what occurs in service as
a result of exposure to temperatures corresponding to those of
the tests.
5. Apparatus
5.1 Heating Plate—The heating plate shall consist of a
corrosion-resistant and heat-resistant plate with a preferred
exposed test area of 36 by 18 in. (914 by 457 mm), but having
a minimum test area of 18 by 18 in. (457 by 457 mm). The
heated area shall have an insulated, heated guard area having a
minimum width of 3 in. (76 mm) around the entire periphery of
the test area. The plate shall be supported in a horizontal plane
at a sufficient number of points to prevent sagging. It shall be
heated on the under side by gas or electricity. The surface
temperature of the plate shall be measured by not less than five
thermocouples. Four of the thermocouples shall be located
along the diagonals that extend from the corners of the exposed
area of the plate and at a distance of 6 in. (152 mm) in from
each corner. A fifth thermocouple shall be located near the
1
This test method is under the jurisdiction of ASTM Committee C16 on Thermal
Insulation and is the direct responsibility of Subcommittee C16.31 on Chemical and
Physical Properties.
Current edition approved March 1, 2019. Published March 2019. Originally
approved in 1958. Last previous edition approved in 2017 as C411 – 17. DOI:
10.1520/C0411-19.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
1
center of the test plate area. The temperature at no point of
measurement shall vary more than 65%or625°F (614°C),
whichever is less, from the desired temperature. A heating
chamber beneath the heating plate shall be formed to retain the
heat generated by the heating means. A 6-in. thickness of
insulation shall form the bottom and the sides, and the heating
plate shall form the top of the chamber. Two suitable types of
heating plates are shown in Fig. 1 and Fig. 2.
5.2 Heating Pipe—The heating pipe shall consist of a
corrosion-resistant and heat-resistant pipe having a length of
not less than 3 ft (0.9 m) and preferably 6 ft 6 in. (1.98 m). It
shall be supported horizontally. The nominal diameter of the
pipe shall preferably be 3 in. (76 mm). The pipe shall be heated
electrically with a spiral heating coil placed along the inside of
the pipe. Supplementary end heaters, and a guard section at
least 3 in. long of the same insulation as that being placed on
the test section, shall also be provided to guard against
excessive losses from the ends of the test specimen. (Where
possible, the use of standard thermal conductivity pipe test
apparatus to serve as the heating pipe is recommended.) The
surface temperature of the pipe shall be measured by means of
thermocouples, not less than one for each 1 ft (0.3 m) of length
of the test specimen, and located spirally around the pipe at 90°
intervals. The test portion of the pipe shall be that area under
a full length of a pipe insulation undergoing test. The tempera-
ture at any point of measurement on the test portion shall not
vary more than 65%or625°F (614°C), whichever is less,
from the desired temperature.
5.3 Temperature Measurement—Thermocouples shall be
used to measure the surface temperature of the heating plate
and the heating pipe. They shall be applied either by peening
the individual wires into small holes drilled into the surface and
separated by not more than
1
⁄
8
in. (3 mm) or by joining the
wires with a welded bead and cementing them in grooves with
the bead tangent to the surface but not projecting above it. The
thermocouples shall be made from wires having a size not
greater than No. 22 Awg (0.644 mm), and preferably not larger
than No. 26 Awg (0.405 mm). The combination of the
thermocouple and measuring instrument used shall ensure an
accuracy of temperature measurement of 61%.
NOTE 1—This requires different thermocouples and measuring instru-
ments for high-temperature tests than for moderate-temperature tests.
5.4 Straightedge and Rule—A straightedge having a length
of at least 36 in. (0.9 m) and a small rule divided in
1
⁄
64
or
1
⁄
10
of 1 in. shall be used to determine warpage.
6. Sampling and Preparation of Test Specimens
6.1 All samples that are required to complete the tests shall
be selected at one time and in such a manner so as to be fully
representative of the average of the material. Test specimens
for any one test condition shall be selected from the original
in.
mm
1
⁄
8
3
1
⁄
4
6
1
⁄
2
13
3
⁄
4
19
1
25
1
1
⁄
2
38
2
51
2
1
⁄
2
64
2
11
⁄
16
68
3
1
⁄
2
89
4
102
4
11
⁄
16
119
5
127
13
330
15
1
⁄
2
394
17
432
18
457
29
737
30
762
31
787
43
1092
45
1143
FIG. 1 Type A Heating Plate for Hot-Surface Performance Test
C411 − 19
2
sample lot so as to be as representative as possible. The test
specimens shall be commercial pieces. For pipe insulation, the
full-size, commercial pipe sections shall be selected. Any
diameter pipe insulation for which equipment is available is
potentially tested. However, only pipe insulation of 3-in.
(76-mm) nominal inside diameter need to be tested.
7. Procedure
7.1 Use the heating plate for testing the flat or block form of
insulation. Use the heating pipe for pipe insulation. The
thickness of the layers in multilayer insulation and the total
thickness of insulation applied to the hot surface for a test shall
be that recommended by the manufacturer for the temperature
of the hot surface in question, or as agreed between the
manufacturer and the purchaser. When multi-layer applications
are to be tested, stagger each joint between adjacent test pieces
in the same layer with respect to the joint in the next layer.
Equally dispose about that joint the test piece in the next layer
that covers a joint of the preceding layer.
7.2 Assembly of Specimen on Heating Plate—Specimens for
testing on a heating plate shall be 6 by 18 in. (152 by 457 mm)
with the thickness as described in 7.1. Check each block for
flatness and measure and record any initial warpage. Cover the
test area of the heating plate with the test blocks. If any blocks
have initial warpage, place the concave face toward the hot
side. Apply additional layers to the first layers when necessary
to give the total required thickness.
7.3 Assembly of Specimen on Heating Pipe—Apply a full
length of pipe insulation to the test pipe. If the test pipe is
longer than the specimen, the latter can advantageously be
centered on the pipe and the ends covered with sawed lengths
of the insulation being tested so as to help guard the full length
specimen from end losses. The thickness of the test specimen
shall be as required in 7.1. Apply additional layers of insulation
as necessary to give the required total thickness. Apply the
various layers of insulation and secure tightly around the pipe
by the usual recommended practice.
3
⁄
16
in. = 4.8 mm
1 ft = 305 mm
24 in. = 610 mm
42 in. = 1067 mm
NOTE 1—Thermocouple leads to temperature controller.
FIG. 2 Type B Heating Plate for Hot-Surface Performance Test
C411 − 19
3
摘要:

ASTM C411 - 19 是用于评估在高温表面条件下绝热材料性能的标准试验方法,主要测试材料在模拟实际使用温度环境下的热稳定性、变形、开裂及脱落等行为。该标准适用于工业设备、管道及锅炉系统中的绝热层,帮助工程人员判断材料能否在持续高温作用下保持结构完整性与隔热效果。通过本标准的测试,用户可以筛选出适用于高温工况的可靠绝热产品,降低因材料失效引发的安全风险与能源损耗,尤其对石油化工、电力及冶金等领域的工程设计与质量控制具有重要参考价值。

展开>> 收起<<
ASTM C411 - 19.pdf

共5页,预览4页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:Carl 分类:国外协会 价格:12星币 属性:5 页 大小:239.56KB 格式:PDF 时间:2024-09-02

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 5
客服
关注