4.2 The thermal resistance of an insulation is related to the
density and thickness of the insulation. It is desirable to obtain
test data on thermal resistances at thicknesses and densities
related to the end uses of the product.
4.3 In normal use, the thickness of these products range
from less than 100 mm (4 in.) to greater than 500 mm (20 in.).
Installed densities depend upon the product type, the installed
thickness, the installation equipment used, the installation
techniques, and the geometry of the insulated space.
4.4 Loose-fill insulations provide coverage information us-
ing densities selected by manufacturers to represent the product
settled densities. Generally, it is necessary to know the product
thermal performance at a representative density. Some cover-
age charts utilize multiple densities to show that greater
thickness installations usually result in higher installed densi-
ties. The use of multiple densities can be detected from the
coverage chart by calculating the density for several different
thermal resistance levels. (The density for a given thermal
resistance can be calculated from the coverage chart by
dividing the minimum mass per unit area by the minimum
thickness.) If the calculated densities are significantly different
at different thermal resistances, the multiple density strategy
has been used.
4.5 When applicable specifications or codes do not specify
the nominal thermal resistance level to be used for comparison
purposes, a recommended practice is to use the R
si
(met-
ric) = 3.3 m
2
K/W (R
IP
=19[hft
2
F/Btu]) label density and
thickness for that measurement.
4.6 If the density for test purposes is not available from the
coverage chart, a test density shall be established by use of
applicable specifications and codes or, if none apply, agreement
between the requesting body and the testing organization.
4.7 Generally, thin sections of these materials are not
uniform. Thus, the test thickness must be greater than or equal
to the product’s representative thickness if the results are to be
consistent and typical of use.
NOTE 1—The representative thickness is specific for each product and
is determined by running a series of tests in which the density is held
constant but the thickness is increased. The representative thickness is
defined here as that thickness above which there is no more than a 2 %
change in the resistivity of the product. The representative thickness is a
function of product blown density. In general, as the density decreases, the
representative thickness increases. Fortunately, most products are de-
signed to be blown over a small range of densities. This limited range
yields a range of representative thicknesses between 100 to 200 mm (4 to
8 in.) for most products. To simplify the process for this Practice, the
representative thickness for the C687 tests shall be determined at the
midpoint of the blown density range. Once this is accomplished, all
thermal testing on this product is conducted at a thickness that is greater
or equal to the representative thickness.
4.7.1 For this practice, the minimum test thickness shall be
100 mm (4 in.) or the representative thickness, whichever is
larger. If the test is to represent an installation at a lesser
thickness, the installed thickness shall be used.
4.8 Because of the high cost of construction and operation
of large test equipment, it is impractical to test at the higher
thicknesses at which products are used. For purposes of this
practice, it is acceptable to estimate the thermal resistance at
any thickness from the thermal resistivity obtained from tests
on the product at the minimum test thickness (see 4.7.1) and at
the density expected for the proposed thickness.
4.9 In principle, any of the standard methods for the
determination of thermal resistance are suitable for loose-fill
products. These include Test Methods C177,C518,C1114, and
C1363. Of these test methods, the heat flow meter apparatus,
Test Method C518, is preferred.
4.10 The thermal resistance of low-density insulations de-
pend upon the direction of heat flow. Unless otherwise
specified, tests shall be performed for the maximum heat flow
condition, that is, a horizontal specimen with heat flow-up.
4.11 Specimens shall be prepared in a manner consistent
with the intended installation procedure. Products for pneu-
matic installation shall be pneumatically applied (blown), and
products for pour-in-place installation shall be poured into
specimen frames.
4.12 Loosefill insulation installed in attic applications will
have heat flow up during the winter. At winter design condi-
tions in many areas, the winter design temperature difference
will cause convective heat transfer to occur within some
loose-fill insulations. The procedure outlined in Practice C687
is not applicable to that measurement unless a Test Method
C1363 test apparatus is used to reproduce the correct boundary
conditions. To determine how seasonal differences can affect
product performance, use Practice C1373. Practice C1373
measures the expected winter thermal performance of loose-fill
insulation under simulated winter design temperature condi-
tions and provides specimen requirements necessary for that
determination.
5. Apparatus
5.1 Thermal test apparatus used for this practice shall meet
these requirements.
5.1.1 Conformance to Standards—The apparatus shall con-
form to all requirements of the ASTM thermal test method
used.
5.1.2 Size and Error—The apparatus shall be capable of
testing specimens up to at least 150-mm (6-in.) thickness with
an estimated error not greater than 1 % attributed to thickness/
guard dimensions. (Parametric studies using a mathematical
model of the proposed apparatus will give insight to this
evaluation. For example see Table 1 in the 1976 revision of
Test Method C518.
3
)
NOTE 2—Thermal test apparatus in use for this practice have overall
plate dimensions of 457 to 1220 mm (18 to 48 in.) square with metering
areas 152 to 457 mm (6 to 18 in.) square. Other sizes are acceptable if
proper consideration of the size-thickness restrictions as outlined in the
test method are observed in their design. (See Practice C1045 for
additional discussion.)
5.1.3 Temperature—As a minimum, the apparatus shall be
capable of testing at a mean temperature of 23.9°C (75°F) with
a temperature difference of 20 to 28°C (36 to 50°F). The
3
See Table 1, “Maximum Spacing Between Warm and Cold Plates of Heat
Flowmeter Apparatus,” of Test Method C518 – 76 published in 1985 Annual Book
of ASTM Standards, Vol 04.06.
C687 − 18
2