gasket installation tools, such as nonmetallic spatulas and
engineered lock-strip insertion devices, are available from the
gasket manufacturer.
4.5 Use of Lubricants—If necessary a lubricant may be
applied to the contact surfaces of the gasket to ease the
installation and help prevent damage to the gasket, glass, or
panel. The lubricant shall be nonstaining, nontoxic,
noncorrosive, chemically stable, compatible with all contact
components, easily removable from exposed surfaces by dry
wiping or with water, and acceptable to the manufacturer of the
supporting frame, panel, and gasket.
4.6 Use of Supplementary Wet Sealants—The use of supple-
mentary wet sealants in conjunction with lock-strip gasket
installations is only required under certain conditions. Such a
condition would occur when the outer lip of the gasket extends
over a butt joint in the supporting frame. The void formed
between the gasket and frame shall be sealed at the time of
installation with a wet sealant. However, the sealant may be
omitted if the system is designed to drain any water that enters
to the exterior, and the omission of a wet sealant is agreeable
to the purchaser and seller. Another condition would be at field
butt joints in gaskets. Such joints require the use of a sealant
installed in, rather than on top of, the joint at the time of the
gasket installation. The wet sealant used, as well as the sealant
manufacturer’s requirements for cleaning and priming the
surfaces to be sealed, shall be compatible with the components
in contact with it and acceptable to the manufacturers of the
components. The use of wet sealants to remedy a defective or
damaged gasket or improperly fabricated supporting frame
shall not be permitted, unless agreeable to the purchaser and
seller.
4.7 Installation of Single-Opening Gasket Systems:
4.7.1 H-Type Gasket—Install the upper gasket corners first,
and then install the lower gasket corners onto the supporting
frame. To avoid slippage, engage both horizontal and vertical
members for about 304.8 mm (1 ft) in both directions from the
corners, and work the gasket until the web is snug against head
and jambs and the corners are square. Then work the remainder
of the gasket onto the supporting frame by starting from each
corner and working towards the center of each side, making
sure the gasket web is firmly seated against the frame and that
the sealing lips are not curled under, particularly at the corners.
Pull each corner of outer flange about 6.4 mm (
1
⁄
4
in.) away
from the supporting frame with thumb or nonmetallic spatula
and then release to ensure uncurling any corner lips hidden
from view.
4.7.2 Reglet-Type Gasket—Insert the upper gasket corners
first, and then install the lower gasket corners into the groove
or reglet of the supporting frame, seating them firmly with a
resiliently faced hammer and a wooden or metal block having
smooth, rounded edges and corners. Then, on each side, insert
the gasket into the groove at the center of each side working
from the center to the corners and from the corners to the
center, equalizing the crowd over the length of each side until
the lips are firmly and continuously seated against the support-
ing frames.
4.8 Installation of Multiple-Opening Gasket Systems (See
Figs. 1 and 2):
4.8.1 Unsupported Vertical Ladder Assembly—Laterally un-
supported vertical ladder type installations as illustrated in Fig.
2, where the vertical load of a light of glass is transferred
through the gasket web to the light below, with lateral support
at the jambs, are not recommended. Refer to Guide C964 for a
discussion of the disadvantages of this type of system.
4.8.2 Unsupported Horizontal Ladder Assembly—Mark on
the head and sill frame members the exact location of the
center line of the vertical gasket muntin. Install the jamb
section first, then work along the head and sill to the first
muntin. Align each gasket muntin with the center lines marked
on the head and sill. Install the glass or panel. The installation
of setting blocks and edge spacers can be performed as
described in 4.10. Then insert the lock-strip at the sill and head,
running to within a few inches of the first gasket muntin.
Continue the procedure by installing the next glass or panel.
Insert the lock-strip into the muntin first and continue with the
insertion of the lock-strip at the head and sill members. Repeat
the procedure until all glass or panels are installed.
4.8.3 Supported Vertical Ladder Assembly—Align and se-
cure the gasket horizontal muntins to the corresponding sup-
porting structural members. The gasket muntins are held in line
by the structural supporting muntin members with the entire
ladder gasket unit completely supported during the installation
procedure.
4.8.4 Supported Horizontal Ladder Assembly—Mount the
gasket to the peripheral frame first. Then align and secure the
vertical gasket muntins to the corresponding structural support-
ing members. Vertical spacer shims are not required between
the glass or panel edge and the gasket web.
4.8.5 Grid Assembly—A grid assembly is a combination of
the horizontal and vertical ladder assemblies. Supported grid
gaskets are mounted to the corresponding frame members
following the procedures noted under 4.8.3 and 4.8.4.
4.9 Installation of Stick System—A proprietary stick system
shall be installed in accordance with the curtain wall manufac-
turer’s instructions.
4.10 Installation of Glass or Panel into Gasket—Inspect,
clean, and dry the gasket as required and replace, if damaged,
before proceeding with the glazing or paneling operation. If
FIG. 1 Gasket Systems
C716 − 06 (2020)
2