Designation: C716 −06 (Reapproved 2020)
Standard Specification for
Installing Lock-Strip Gaskets and Infill Glazing Materials
1
This standard is issued under the fixed designation C716; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers installation procedures for
lock-strip gaskets that comply with Specification C542 and for
infill glazing materials in lockstrip gasket glazing applications
used in building walls which are not more than 15° from a
vertical plane. The prime performance considerations are
weathertightness against air and water infiltration, and struc-
tural integrity under wind loads.
1.2 The values stated in SI units are to be regarded as
standard. The values given in parentheses are provided for
information only.
1.3 The committee with jurisdiction over this standard is not
aware of any comparable standards published by other orga-
nizations.
1.4 This international standard was developed in accor-
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
2
C542 Specification for Lock-Strip Gaskets
C717 Terminology of Building Seals and Sealants
C963 Specification for Packaging, Identification, Shipment,
and Storage of Lock-Strip Gaskets
C964 Guide for Lock-Strip Gasket Glazing
3. Significance and Use
3.1 This specification can be referred to in contract docu-
ments as a method and workmanship standard for the installa-
tion of lock-strip gasket glazing systems. See also related
standards (Specifications C542 and C963, Guide C964, and
Terminology C717).
4. Installation
4.1 Inspection of Components—Before installing gaskets,
the installer shall check the mounting frames to see that they
are within specified dimensional tolerances and not out-of-
square or plane, and check all gaskets for type, dimensions, and
defects such as misalignment at molded corners and damaged
lips. Installation shall not proceed until corrections have been
made.
4.2 Environmental Conditions—Maximum efficiency and
sealing capability of gaskets is achieved in a clean, dry, warm
environment, with the gasket kept resilient during the entire
installation process. During cold weather the use of temporary
enclosures around the units to be glazed or paneled will
facilitate temperature control and also aid in keeping open
gasket channels clean and dry.
4.3 Preparation and Conditioning of Gaskets—Lock-strip
gaskets require conditioning prior to installation in order to
restore maximum resiliency and remove deformations after
prolonged storage in a coiled or stressed position. Gaskets shall
be unpacked from their containers and conditioned for 24 h in
a temperature not lower than 21.1 °C (70 °F) by being placed
flat or hung on racks to permit recovery of their original
shapes. Racks shall be free of rough surfaces, projections,
sharp edges, and other conditions that could damage the
gaskets. When the ambient temperature is 10 °C (50 °F) or
below and a heated space is not available, gaskets shall be
heated by other means to remove deformations and provide a
high degree of flexibility and resiliency. This may be done by
warming them in hot water or heated containers. Gaskets shall
not be heated by being draped over heated units or placed in
direct contact with a flame or fired heating device. The
installation of glass, panel, and lock-strip shall be completed
while the gasket is still warm and pliable and with the gasket
channels clean and dry.
4.4 Use of Tools—To minimize the possibility of damage,
sharp or pointed tools or implements such as screwdrivers or
putty knives shall not be used on lock-strip gaskets. Suitable
1
This specification is under the jurisdiction of ASTM Committee C24 on
Building Seals and Sealantsand is the direct responsibility of Subcommittee C24.73
on Compression Seal and Lock Strip Gaskets.
Current edition approved Jan. 1, 2020. Published January 2020. Originally
approved in 1973. Last previous edition approved in 2015 as C716 – 06 (2015).
DOI: 10.1520/C0716-06R20.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
gasket installation tools, such as nonmetallic spatulas and
engineered lock-strip insertion devices, are available from the
gasket manufacturer.
4.5 Use of Lubricants—If necessary a lubricant may be
applied to the contact surfaces of the gasket to ease the
installation and help prevent damage to the gasket, glass, or
panel. The lubricant shall be nonstaining, nontoxic,
noncorrosive, chemically stable, compatible with all contact
components, easily removable from exposed surfaces by dry
wiping or with water, and acceptable to the manufacturer of the
supporting frame, panel, and gasket.
4.6 Use of Supplementary Wet Sealants—The use of supple-
mentary wet sealants in conjunction with lock-strip gasket
installations is only required under certain conditions. Such a
condition would occur when the outer lip of the gasket extends
over a butt joint in the supporting frame. The void formed
between the gasket and frame shall be sealed at the time of
installation with a wet sealant. However, the sealant may be
omitted if the system is designed to drain any water that enters
to the exterior, and the omission of a wet sealant is agreeable
to the purchaser and seller. Another condition would be at field
butt joints in gaskets. Such joints require the use of a sealant
installed in, rather than on top of, the joint at the time of the
gasket installation. The wet sealant used, as well as the sealant
manufacturer’s requirements for cleaning and priming the
surfaces to be sealed, shall be compatible with the components
in contact with it and acceptable to the manufacturers of the
components. The use of wet sealants to remedy a defective or
damaged gasket or improperly fabricated supporting frame
shall not be permitted, unless agreeable to the purchaser and
seller.
4.7 Installation of Single-Opening Gasket Systems:
4.7.1 H-Type Gasket—Install the upper gasket corners first,
and then install the lower gasket corners onto the supporting
frame. To avoid slippage, engage both horizontal and vertical
members for about 304.8 mm (1 ft) in both directions from the
corners, and work the gasket until the web is snug against head
and jambs and the corners are square. Then work the remainder
of the gasket onto the supporting frame by starting from each
corner and working towards the center of each side, making
sure the gasket web is firmly seated against the frame and that
the sealing lips are not curled under, particularly at the corners.
Pull each corner of outer flange about 6.4 mm (
1
⁄
4
in.) away
from the supporting frame with thumb or nonmetallic spatula
and then release to ensure uncurling any corner lips hidden
from view.
4.7.2 Reglet-Type Gasket—Insert the upper gasket corners
first, and then install the lower gasket corners into the groove
or reglet of the supporting frame, seating them firmly with a
resiliently faced hammer and a wooden or metal block having
smooth, rounded edges and corners. Then, on each side, insert
the gasket into the groove at the center of each side working
from the center to the corners and from the corners to the
center, equalizing the crowd over the length of each side until
the lips are firmly and continuously seated against the support-
ing frames.
4.8 Installation of Multiple-Opening Gasket Systems (See
Figs. 1 and 2):
4.8.1 Unsupported Vertical Ladder Assembly—Laterally un-
supported vertical ladder type installations as illustrated in Fig.
2, where the vertical load of a light of glass is transferred
through the gasket web to the light below, with lateral support
at the jambs, are not recommended. Refer to Guide C964 for a
discussion of the disadvantages of this type of system.
4.8.2 Unsupported Horizontal Ladder Assembly—Mark on
the head and sill frame members the exact location of the
center line of the vertical gasket muntin. Install the jamb
section first, then work along the head and sill to the first
muntin. Align each gasket muntin with the center lines marked
on the head and sill. Install the glass or panel. The installation
of setting blocks and edge spacers can be performed as
described in 4.10. Then insert the lock-strip at the sill and head,
running to within a few inches of the first gasket muntin.
Continue the procedure by installing the next glass or panel.
Insert the lock-strip into the muntin first and continue with the
insertion of the lock-strip at the head and sill members. Repeat
the procedure until all glass or panels are installed.
4.8.3 Supported Vertical Ladder Assembly—Align and se-
cure the gasket horizontal muntins to the corresponding sup-
porting structural members. The gasket muntins are held in line
by the structural supporting muntin members with the entire
ladder gasket unit completely supported during the installation
procedure.
4.8.4 Supported Horizontal Ladder Assembly—Mount the
gasket to the peripheral frame first. Then align and secure the
vertical gasket muntins to the corresponding structural support-
ing members. Vertical spacer shims are not required between
the glass or panel edge and the gasket web.
4.8.5 Grid Assembly—A grid assembly is a combination of
the horizontal and vertical ladder assemblies. Supported grid
gaskets are mounted to the corresponding frame members
following the procedures noted under 4.8.3 and 4.8.4.
4.9 Installation of Stick System—A proprietary stick system
shall be installed in accordance with the curtain wall manufac-
turer’s instructions.
4.10 Installation of Glass or Panel into Gasket—Inspect,
clean, and dry the gasket as required and replace, if damaged,
before proceeding with the glazing or paneling operation. If
FIG. 1 Gasket Systems
C716 − 06 (2020)
2
necessary, a lubricant recommended by the gasket manufac-
turer can be used to aid insertion. Lubricate the surface of the
exterior flange on the lock-strip side of the gasket channel that
is to receive the glass or panel. Beginning approximately 152.4
to 203.2 mm (6 to 8 in.) above the bottom, open the channel
lips and engage both lower corners of the glass or panel into the
gasket sides and then lower it carefully into the sill channel of
the gasket. Maintain the plane of the panel as close to the plane
of the opening as possible. Insert a nonmetallic spatula
between the edge of the glass or panel and the sealing lip on
each side, starting at the bottom of the opening. Proceed
upward with both spatulas at the same time, while simultane-
ously pushing the glass or panel lightly inward. Use care to
prevent cutting of gasket-sealing lips. When the glass or panel
is in jamb channels to within 50.8 to 76.2 mm (2 to 3 in.) of
uppercorners, begin at the center of the head and work outward
each way to engage the head channel. Then, using two spatulas,
lift gasket corners over the edge of the glass or panel. Center
the glass or panel in the gasket for uniform edge coverage on
both sides of the installation. At this time install properly sized
setting blocks, if required, by lifting the glass or panel and
placing them at the quarter points. Lower the glass or panel
onto the blocks, being careful not to displace them. Setting
blocks under panels are optional but are required for laminated,
insulating, annealed tinted, and reflective glass. The use of
setting blocks for other types of glass products shall be in
accordance with the glass manufacturer’s recommendations. If
necessary, edge spacers may be installed at this time to
maintain uniform edge clearance and to preclude lateral
displacement of the glass or panel.
4.11 Installation of Lock-Strip—As soon as the glass and
panels are in place, install the lock-strip so that the assembly is
secure and the gasket channel is sealed. Cut lock-strip for the
sill to a length approximately 50.8 to 76.2 mm (2 to 3 in.)
longer than the sill opening dimension. Lubricate the lock-strip
and lock-strip cavity. Thread the lock-strip into the eye of the
insertion tool. Start installation of the lock-strip at the sill,
trying to keep it under compression instead of tension and
leaving an excess of lock-strip at both ends. Repeat this
procedure for jambs and head. To avoid any later creep or
drawback of the lock-strip from the corners, trim the lock-strip
ends approximately 3.2 to 6.4 mm (
1
⁄
8
to
1
⁄
4
in.) longer than the
lock-strip cavity using garden pruning shears or diagonal
cutters, and crowd the lock-strip into place using a nonmetallic
tool. Either a mitre or square butt joint is acceptable. When
molded lock-strip corners are used, install them first and form
butt joints with the lock-strip in compression between the
corners.
4.12 Completing the Installation—To straighten the
sightline, tap the gasket against the frame using a clean, smooth
block of wood. Push the lock-strip into the cavity with a
spatula wherever complete insertion was not accomplished.
Wipe off excess lubricant. Inspect and rectify any curled-under
lips. Contact of the gasket with the frame and panel or glass
shall be continuous and positive against smooth flat surfaces.
5. Keywords
5.1 elastomer; gasket; glazing; installation; lock-strip; pre-
formed infill; procedures
A Setting blocks
BWeb
C Spacer shims
D Laterally supporting muntin
E Vertical load transfer through setting blocks, web, and spacer shims to glass light below is not recommended
F Vertical load transfer through setting blocks and web to supporting muntin is recommended
G Laterally and vertically supporting muntin
FIG. 2 Vertical Ladder Assembly Horizontal Muntin
C716 − 06 (2020)
3
摘要:

ASTM C716 - 06 (2020) 是美国材料与试验协会发布的一项关于金属反射型隔热毯的标准规范,该标准最初于2006年批准,并于2020年进行了确认和重新批准,适用于高温工业设备、管道及航空领域的隔热应用。该规范详细规定了金属箔与隔热材料复合毯的结构、尺寸公差、热性能、耐久性及安装要求,强调其在极端温度环境下的反射热辐射能力和抗机械应力性能。适用于需要高效隔热、防火及轻量化解决方案的工程场景,如发电厂、化工装置及航空航天系统。符合该标准的产品可确保长期使用中的热稳定性、耐腐蚀性及抗振动

展开>> 收起<<
ASTM C716 - 06 (2020).pdf

共4页,预览4页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:Carl 分类:国外协会 价格:12星币 属性:4 页 大小:112.54KB 格式:PDF 时间:2024-09-02

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 4
客服
关注