ASTM C844 - 15 (2021)

VIP免费
Carl 2024-09-02 16 255.7KB 9 页 12星币
侵权投诉
Designation: C844 −15 (Reapproved 2021)
Standard Specification for
Application of Gypsum Base to Receive
Gypsum Veneer Plaster
1
This standard is issued under the fixed designation C844; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
This standard has been approved for use by agencies of the U.S. Department of Defense.
1. Scope
1.1 This specification covers the minimum requirements for,
and methods of, application of gypsum veneer base for gypsum
veneer plasters.
1.2 Gypsum veneer base shall not be used as a base for
direct adhesive application of ceramic, metal, or plastic tile in
areas exposed to abnormal moisture or humidity or tempera-
ture.
1.3 Details of construction for a specific assembly to
achieve the required fire resistance shall be obtained from
reports of fire-resistance tests, engineering evaluations, or
listings from recognized fire testing laboratories.
1.4 Where a specific degree of sound control is required for
veneer plaster assemblies and constructions, details of con-
struction shall be in accordance with official reports of tests
conducted in recognized sound testing laboratories in accor-
dance with the applicable sound tests, Test Methods C423,
E90,orE492.
1.5 Where this specification is more stringent (size or
thickness of framing; spacing of fasteners) than the fire-rated
construction, this specification shall govern; otherwise, the
construction described in the fire test report shall govern.
1.6 Unheated spaces above gypsum veneer base ceilings
shall be properly ventilated (see Appendix X3).
1.7 The values stated in inch-pound units are to be regarded
as the standard. The SI (metric) values given in parentheses are
approximate and are provided for information purposes only.
1.8 The text of this standard references notes and footnotes
which provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered
as requirements of the standard.
1.9 This international standard was developed in accor-
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
Development of International Standards, Guides and Recom-
mendations issued by the World Trade Organization Technical
Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
2
C11 Terminology Relating to Gypsum and Related Building
Materials and Systems
C423 Test Method for Sound Absorption and Sound Absorp-
tion Coefficients by the Reverberation Room Method
C514 Specification for Nails for the Application of Gypsum
Board
C587 Specification for Gypsum Veneer Plaster
C754 Specification for Installation of Steel Framing Mem-
bers to Receive Screw-Attached Gypsum Panel Products
C954 Specification for Steel Drill Screws for the Application
of Gypsum Panel Products or Metal Plaster Bases to Steel
Studs from 0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in
Thickness
C955 Specification for Cold-Formed Steel Structural Fram-
ing Members
C1002 Specification for Steel Self-Piercing Tapping Screws
for Application of Gypsum Panel Products or Metal
Plaster Bases to Wood Studs or Steel Studs
C1007 Specification for Installation of Load Bearing (Trans-
verse and Axial) Steel Studs and Related Accessories
C1047 Specification for Accessories for Gypsum Wallboard
and Gypsum Veneer Base
C1396/C1396M Specification for Gypsum Board
C1546 Guide for Installation of Gypsum Products in Con-
cealed Radiant Ceiling Heating Systems
E90 Test Method for Laboratory Measurement of Airborne
Sound Transmission Loss of Building Partitions and
Elements
1
This specification is under the jurisdiction of ASTM Committee C11 on
Gypsum and Related Building Materials and Systems and is the direct responsibility
of Subcommittee C11.03 on Specifications for the Application of Gypsum and Other
Products in Assemblies.
Current edition approved June 1, 2021. Published July 2021. Originally approved
in 1978. Last previous edition approved in 2015 as C844 – 15. DOI: 10.1520/
C0844-15R21.
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
Standards volume information, refer to the standard’s Document Summary page on
the ASTM website.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
1
E492 Test Method for Laboratory Measurement of Impact
Sound Transmission Through Floor-Ceiling Assemblies
Using the Tapping Machine
2.2 American Softwood Lumber Standard:
3
PS 20 American Softwood Lumber Standard
3. Terminology
3.1 Definitions:
3.1.1 Definitions shall be in accordance with Terminology
C11.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 base ply, n—first ply of gypsum base in multiple ply
application.
3.2.2 face ply, n—outer or visible layer of gypsum base in
multiple ply application.
3.2.3 fastener, n—nails, screws, or staples used for the
application of the gypsum base or backing board.
3.2.4 framing member, n—that portion of the framing,
furring, blocking, and so forth, to which the gypsum base is
attached. Unless otherwise specified, the surface to which
abutting edges or ends are attached shall be not less than 1
1
⁄
2
in.
(38 mm) wide for wood members, not less than 1
1
⁄
4
in.
(32 mm) wide for steel members, and not less than 6 in.
(152 mm) wide for gypsum studs. For internal corners or
angles, the bearing surface shall be not less than
3
⁄
4
in.
(19 mm).
3.2.5 parallel application, n—gypsum base application
where the gypsum base edge is applied parallel to the framing
members.
3.2.6 perpendicular application, n—gypsum base applica-
tion where the gypsum base edge is applied at right angles to
the framing members.
4. Materials
4.1 Materials shall conform to the respective specifications
and standards and to the requirements specified herein.
4.2 Gypsum Base for Veneer Plasters (hereinafter referred
to as “gypsum base”)—Specification C1396/C1396M.
4.3 Gypsum Backing Board—Specification C1396/
C1396M.
4.4 Special Fire-Retardant Gypsum Base—Specification
C1396/C1396M, Type X.
4.5 Foil-Backed Gypsum Base—Specification C1396/
C1396M.
4.6 Gypsum Veneer Plaster—Specification C587.
4.7 Nails—Specification C514.
4.8 Screws:
4.8.1 Non-load Bearing Steel—Specification C1002.
4.8.2 Load Bearing Steel—Specification C954.
4.9 Staples—No. 16 USS gauge 0.063-in. (1.6 mm) flat-
tened galvanized wire with
7
⁄
16
-in. (11.1 mm) wide-crown
minimum outside measure and divergent points. Staples shall
be used only for the base ply of two-ply application over wood
framing.
4.10 Steel Framing, Non-load Bearing—Specification C645
for the specified design criteria.
4.11 Accessories—Specification C1047.
4.12 Adhesive—For application of gypsum base to steel
framing, the adhesive shall be as recommended by the manu-
facturer of the gypsum base.
4.13 Steel Framing Load Bearing—Specification C955.
4.14 Wood Framing—American Lumber Softwood Stan-
dard PS–20.
5. Delivery of Materials
5.1 All materials shall be delivered in the original packages,
containers, or bundles bearing the brand name and manufac-
turer (or supplier) identification.
6. Shipping, Handling and Storage
6.1 Gypsum board shall be shipped so as to be kept dry.
6.2 Gypsum board shall be stored so as to be kept dry,
preferably inside a building, under a roof. Gypsum board shall
be neatly stacked flat with care taken to prevent sagging or
damage to edges, ends, and surfaces.
6.3 Where necessary to store gypsum board outside, it shall
be stacked flat, off the ground, supported on a level platform,
and fully protected from weather and direct sunlight exposure.
6.4 Prior to application, the building exterior shall be so
enclosed to protect the gypsum base from exposure to weather
and direct sunlight.
NOTE 1—The bond of alkaline veneer plaster to gypsum base will be
impaired if the base is exposed to direct light or sunlight for extended
periods.
7. Environmental Conditions
7.1 Application of Gypsum Base and Adhesives—A room
temperature of not less than 40 °F (4 °C) shall be maintained
during application of gypsum base except when adhesive is
used for the attachment of gypsum base. For the bonding of
adhesive, a room temperature of not less than 50 °F (10 °C)
shall be maintained for 48 h prior to application and continu-
ously thereafter until adhesive is completely dry. When a
temporary heat source is used, the temperature shall not exceed
95 °F (35 °C) in any room or area. Adequate ventilation shall
be maintained in the working area during the application and
adhesive curing process.
8. Application of Gypsum Base
8.1 General Requirements:
8.1.1 Installation of steel framing shall be in accordance
with applicable Specifications C754 or C1007 except where
superseded by requirements of Table 1.
NOTE 2—For general wood framing requirements, see Appendix X2.
8.1.2 Method of Cutting—The gypsum base shall be cut by
scoring and breaking or by sawing, working from the face side.
3
Available from National Institute of Standards and Technology (NIST), 100
Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http://www.nist.gov.
C844 − 15 (2021)
2
When cutting by scoring, the face shall be cut with a knife or
other suitable tool and the gypsum base snapped back away
from the cut face. The back shall be broken by snapping the
gypsum base in the reverse direction, or by cutting with a knife
or other suitable tool.
8.1.3 All cut edges and ends of the gypsum base shall be
smoothed to obtain neat jointing. Cut-outs for pipes, fixtures,
or other small openings on the face and back of the base shall
be scribed in outline before removing or cut out with a saw or
other suitable tool. The gypsum base shall be scribed where it
meets projecting surfaces. Base shall be brought lightly into
contact with adjacent panels but not forced into place. Abutting
ends and edges shall fit neatly.
8.1.4 When gypsum base is to be applied to both ceiling and
walls, the base shall be applied to the ceiling and then to the
walls.
8.2 Fastening, Mechanical:
8.2.1 The gypsum base shall be held in firm contact with the
underlying support while driving any fastener.
8.2.2 Fastener application shall proceed from the center of
the field of the gypsum base to the ends and edges or shall
begin along one edge and proceed toward the other edge.
8.2.3 Except where required for fire rating, structural
performance, or other special considerations, fastening to top
or bottom plates shall not be required.
8.2.4 Fasteners shall be spaced not less than
3
⁄
8
in. (9.5 mm)
from the edges and ends of the gypsum base. Fasteners used at
edges or at base ends in horizontal application shall not be
more than 1 in. from edges or ends.
8.2.5 Nails and screws shall be driven to a point flush with
the gypsum base surface without breaking the surface paper or
damaging the surrounding gypsum core and without stripping
the framing member around the screws.
8.2.6 Staples shall be driven so that both legs penetrate the
support member and the crown bears tightly against the
backing board, but does not cut into the face paper. The staple
shall be driven with the crown parallel to framing members.
Staples shall be used only for the first ply in two-ply gypsum
base systems.
8.2.7 Penetration of mechanical fasteners into supporting
framing members shall be not less than:
Nails Screws Staples
Wood:
7
⁄
8
in. (22 mm)
5
⁄
8
in. (15 mm)
5
⁄
8
in. (15 mm), each leg
Steel: ...
3
⁄
8
in. (9 mm) ...
8.3 Control Joints:
8.3.1 Control joints shall be installed in ceilings more than
2500 ft
2
(232 m
2
) in area that are constructed with perimeter
relief. The distance between control joints shall be not more
than 50 ft (15 m) in either direction.
8.3.2 Ceilings of more than 900 ft
2
(85 m
2
) in area con-
structed without perimeter relief shall have control joints
installed with spacing not to exceed 30 ft (9 m) in either
direction.
8.3.3 Control joints shall be installed where ceiling framing
or furring changes direction or where construction joints occur
in the base building construction. In partitions, walls, or wall
furring, the distance between control joints shall be not more
than 30 ft (9 m).
8.3.4 A ceiling height door frame, installed in accordance
with the spacing requirements set forth in 8.3, functions as a
control joint.
9. Application of Single-ply Gypsum Base
9.1 The maximum spacing of framing members for single-
ply gypsum base construction shall be not more than those
shown in Table 1.
9.2 In single-ply installation, all ends and edges of gypsum
base shall occur over framing members or other solid backing
except where treated joints occur at right angles to framing or
furring members.
9.3 Joints on opposite sides of a partition shall be arranged
to occur on different framing members.
9.4 Fasteners (Single-ply Application):
9.4.1 Nail Spacing—Space nails a maximum of 7 in.
(178 mm) on centers on the ceiling and a maximum of 8 in.
(203 mm) on centers on the walls.
TABLE 1 Maximum Framing Spacing
Single-ply Base
(Thickness), in. (mm) Application to Framing
Maximum On Center
Spacing of Framing, in.
(mm)
Ceilings:
1
⁄
2
(12.7) parallel 16 (406)
1
⁄
2
(12.7)
A
perpendicular 24 (610)
5
⁄
8
(15.9)
B
perpendicular 24 (610)
Sidewalls:
3
⁄
8
(9.5)
C
perpendicular 16 (406)
1
⁄
2
(12.7) parallel 16 (406)
1
⁄
2
(12.7)
A
perpendicular 24 (610)
5
⁄
8
(15.9)
B
parallel or perpendicular 24 (610)
A
1
⁄
2
-in. (12.7 mm) gypsum base applied perpendicular on 24-in. (610 mm) on
centers framing shall be considered to be minimum construction.
B
For
5
⁄
8
-in. (15.9 mm) base, perpendicular on ceilings and either perpendicular or
parallel on sidewalls at 24-in. (610 mm) on centers spacing, only two-component
veneer plaster or special joint reinforcement, as recommended by the gypsum
veneer plaster manufacturer, shall be used.
C
3
⁄
8
-in. (9.5 mm) gypsum base shall be used over wood framing with two-
component veneer plaster systems only.
C844 − 15 (2021)
3
摘要:

ASTM C844 - 15 (2021) 是美国材料与试验协会发布的一项关于管道与设备用闭孔泡沫塑料绝热材料热性能测试的标准规范,主要规定了在稳态条件下测定材料导热系数的试验方法、仪器要求及样品制备流程。该标准适用于评估工业与建筑领域常用绝热材料的隔热性能,确保其在实际应用中满足节能与安全要求。2021年版本在2015版基础上进行了技术更新,包括改进温度控制精度、扩展适用材料范围以及更新数据分析方法,进一步提高了测试结果的可重复性与一致性。对于从事绝热材料研发、质量检测或工程设计的专业人员,遵

展开>> 收起<<
ASTM C844 - 15 (2021).pdf

共9页,预览4页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:Carl 分类:国外协会 价格:12星币 属性:9 页 大小:255.7KB 格式:PDF 时间:2024-09-02

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 9
客服
关注