3. Terminology
3.1 Definitions—For definitions of terms relating to
insulation, refer to Terminology C168.
4. Classification
4.1 The flexible fibrous glass insulation is furnished in two
types, as follows:
4.1.1 Type I—Glass processed from the molten state into
fibrous form, bonded with a thermosetting resin, and formed
into a blanket or batt.
4.1.2 Type II—Type I material supplied with a suitable
facing adhered to one surface.
NOTE 1—Facing properties are not part of this specification. The
designer is referred to Practice C755 and Specification C1136 for
guidance in selecting water vapor permeance and other physical property
requirements.
5. Ordering Information
5.1 Type I material shall be ordered by specifying thermal
resistance value, length, and width.
5.2 Type II material shall be ordered by specifying thermal
resistance value, type of facing, facing permeance, length,
width, number of tabs, and tab width.
5.3 Certification, when required, shall be in accordance with
Section 11.
6. Physical Properties
6.1 Type 1 Material:
6.1.1 The unfaced insulation shall meet the following re-
quirements:
6.1.1.1 Thermal Resistance—The average R-value of nine
tests, one each performed on three randomly selected speci-
mens from each of three rolls, shall be not less than 103 % of
the R-value agreed upon by the purchaser and the supplier.
(1) The average thickness of each roll shall be determined
by Test Method C167 and the lesser of measured or labeled
thickness tested.
(2) The thermal resistance of the pre-processed (unlami-
nated) insulation shall be determined in accordance with Guide
C653, using Practice C1045 and either Test Method C177 or
C518 at a mean temperature of 75°F (23.9°C) with a minimum
temperature difference of 40°F (22°C) for determining the
apparent thermal conductivity.
NOTE 2—See Guide C653. The thermal resistance is a function of
temperature. As an option, the thermal resistance may be determined at
additional temperatures as agreed upon by the purchaser and the manu-
facturer.
6.1.2 Surface Burning Characteristics—The unfaced insu-
lation shall exhibit a flame spread index not exceeding 25 and
a smoke developed index not exceeding 50 when tested in
accordance with either Test Method E84, with specimens
prepared and mounted per Practice E2988, or with CAN/ULC
S102, depending on the applicable code requirements.
6.1.3 Combustion Characteristics—The material shall pass
the requirements of Test Method E136.
6.1.4 Water Vapor Sorption—The water vapor sorption from
exposure to water vapor shall not be greater than 0.2 % by
volume when determined in accordance with the procedure set
forth in Test Method C1104/C1104M.
6.1.5 Fungi Resistance—When tested in accordance with
the procedure set forth in Test Method C1338, the insulation
shall exhibit no growth.
6.1.6 Corrosiveness:
6.1.6.1 When tested in accordance with the procedure in
Specification C665, the metal plates in contact with the
insulation shall show no greater corrosion than that observed
on the comparative plates in contact with sterile cotton.
6.1.6.2 Alternative Test (for steel only)—When tested in
accordance with the procedure in Practice C1617, the mass loss
corrosion rate of the unfaced insulation extract shall not exceed
that of the 5 ppm chloride solution.
NOTE 3—The testing of other metals such as copper and aluminum is
being evaluated using Practice C1617. The task group will continue to
investigate the potential for using this practice as an alternative to section
13.8 of Specification C665 for these metals.
6.1.7 Odor Emission—When tested in accordance with Test
Method C1304, the insulation shall not emit a detectable odor
objectionable to more than two of the five panel members.
6.1.8 Dimensional Tolerances—The average measured
length and width shall not differ from the manufacturer’s
standard dimensions, when determined in accordance with Test
Methods C167, (Note 4) by more than the following:
Length,− 0 in. (−0 mm)
Width, −
1
⁄
8
in. (−3 mm)
NOTE 4—Normally, a slight excess in all dimensions will be permitted.
However, the purchaser may elect to specify a maximum tolerance to meet
further processing requirements.
6.2 Type II Material:
6.2.1 Type II shall consist of a Type I blanket laminated
with a facing.
6.2.1.1 The facing shall meet the requirements of Specifi-
cation C1136 for corrosion resistance, fungi resistance, and
non-leachability (permanence) of flame retardants, as certified
by the facing supplier.
6.2.2 The faced insulation shall meet the following require-
ments:
6.2.2.1 Thermal Resistance—The average R-value of nine
tests, one each performed on three randomly selected speci-
mens from each of three rolls, shall be not less than 95 % of the
R-value agreed upon by the purchaser and the supplier.
(1) The average thickness of each roll shall be determined
by Test Method C167 and the lesser of measured or labeled
thickness tested.
(2) The thermal resistance of the post- laminated insulation
shall be determined in accordance with Guide C653, using
Practice C1045 and either Test Method C177 or Test Method
C518 at 75°F (23.9°C) with a minimum temperature difference
of 40°F (22°C) for determining the apparent thermal conduc-
tivity.
6.2.2.2 Surface Burning Characteristics—The faced insula-
tion shall exhibit a flame spread index not exceeding 25 and a
smoke developed index no exceeding 50 when tested on the
facing side in accordance with either Test Method E84, with