of the materials and ingredients used in the test specimen shall
be determined and recorded.
5.2 The size and dimensions of the test specimen specified
herein shall apply for classifying constructions of dimensions
within the range employed in buildings. When the conditions
of use limit the construction to smaller dimensions, the
dimensions of the test specimen shall be reduced proportion-
ately for a test qualifying them for such restricted use.
5.3 Test specimens designed with a built-up roof shall be
tested with a roof covering of 3 ply, 15 lb (6.8 kg) type felt,
with not more than 120 lb (54 kg) per square 100 ft
2
(9 m
2
) of
hot mopping asphalt without gravel surfacing. Tests with this
covering do not preclude the field use of other coverings with
a larger number of plys of felt, with a greater amount of asphalt
or with gravel surfacing.
5.4 Roofing systems designed for other than the use of
built-up roof coverings shall be tested using materials and
details of construction representative of field application.
6. Protection and Conditioning of Test Specimen
6.1 Protect the test specimen during and after fabrication to
ensure its quality and condition at the time of test. The test
specimen shall not be tested until its required strength has been
attained, and, until an air-dry condition has been achieved in
accordance with the requirements given in 6.2 – 6.4. Protect
the testing equipment and test specimen undergoing the fire-
resistance test from any condition of wind or weather that is
capable of affecting results. The ambient air temperature at the
beginning of the test shall be within the range of 50 °F to 90 °F
(10 °C to 32 °C). The velocity of air across the unexposed
surface of the test specimen, measured just before the test
begins, shall not exceed 4.4 ft (1.3 m/s), as determined by an
anemometer placed at right angles to the unexposed surface.
When mechanical ventilation is employed during the test, an
air stream shall not be directed across the surface of the test
specimen.
6.2 Prior to the fire-resistance test, condition test specimens
with the objective of providing moisture condition within the
test specimen representative of that in similar construction in
buildings. For purposes of standardization, this condition is
established at equilibrium resulting from conditioning in an
ambient atmosphere of 50 % relative humidity at 73 °F (23 °C)
(Note 1).
6.2.1 With some constructions it is difficult or impossible to
achieve such uniformity. Where this is the case, test specimens
are tested when the dampest portion of the test specimen, or the
portion at 6 in. (152 mm) depth below the surface of massive
constructions, has achieved a moisture content corresponding
to conditioning to equilibrium with air in the range of 50 % to
75 % relative humidity at 73 °F 65 °F (23 °C 63 °C).
6.2.2 When evidence is shown that test specimens condi-
tioned in a heated building will fail to meet the requirements of
6.2 after a 12-month conditioning period, or in the event that
the nature of the construction is such that it is evident that
conditioning of the test specimen interior is prevented by
hermetic sealing, the moisture condition requirements of 6.2
are permitted to be waived, and either 6.2.2.1 or 6.2.2.2 shall
apply.
6.2.2.1 Alternative conditioning methods are permitted to
be used to achieve test specimen equilibrium prescribed in 6.2
(Note 2), or
6.2.2.2 The specimen tested when its strength is at least
equal to its design strength after a minimum 28 day condition-
ing period.
6.3 Avoid conditioning procedures that will alter the struc-
tural or fire-resistance characteristics of the test specimen from
those produced as the result of conditiong in accordance with
procedures given in 6.2.
6.4 Information on the actual moisture content and distri-
bution within the test specimen shall be obtained within 72 h
prior to the fire. Include this information in the test report (Note
3).
NOTE 1—A recommended method for determining the relative humidity
within a hardened concrete test specimen with electric sensing elements is
described in Appendix I of the paper by Menzel, C. A., “A Method for
Determining the Moisture Condition of Hardened Concrete in Terms of
Relative Humidity,” Proceedings, ASTM, Vol 55, 1955, p. 1085. A similar
procedure with electric sensing elements is permitted to be used to
determine the relative humidity within test specimens made with other
materials.
With wood constructions, the moisture meter based on the electrical
resistance method can be used, when appropriate, as an alternative to the
relative humidity method to indicate when wood has attained the proper
moisture content. Electrical methods are described on page 12-2 of the
1999 edition of the Wood Handbook of the Forest Products Laboratory,
U.S. Department of Agriculture. The relationships between relative
humidity and moisture content are given in Table 3-4 on p. 3-7. This
indicates that wood has a moisture content of 13 % at a relative humidity
of 70 % for a temperature of 70 °F to 80 °F (21 °C to 27 °C).
NOTE 2—An example where alternative conditioning may be employed
is where concrete specimens are conditioned at elevated temperatures in a
“heated building” to more rapidly obtain the conditions described in 6.2.
In such cases, temperatures other than 73 °F (23 °C) are used to reach a
maximum 50 % relative humidity.
NOTE 3—If the moisture condition of the test specimen is likely to
change drastically from the 72-h sampling time prior to test, the sampling
should be made not later than 24 h prior to the test.
7. Control
7.1 Fire-Resistance Test:
7.1.1 Time-Temperature Curve:
7.1.1.1 The furnace temperatures shall be controlled to
follow the standard time-temperature curve shown in Fig. 1.
The points on the curve that determine its character are:
1000 °F (538 °C) at 5 min
1300 °F (704 °C) at 10 min
1550 °F (843 °C) at 30 min
1700 °F (927 °C) at 1 h
1850 °F (1010 °C) at 2 h
2000 °F (1093 °C) at 4 h
2300 °F (1260 °C) at 8 h or over
7.1.1.2 For a more detailed definition of the time-
temperature curve, see Appendix X1.
NOTE 4—Recommendations for Recording Fuel Flow to Furnace
Burners— The following provides guidance on the desired characteristics
of instrumentation for recording the flow of fuel to the furnace burners.
Fuel flow data may be useful for a furnace heat balance analysis, for
measuring the effect of furnace or control changes, and for comparing the
E119 − 26
3