NEMA US 80018-2022 设计规范考虑因素与建议

VIP专免
小气猫 2026-09-27 12 180.2KB 5 页 25星币
侵权投诉
NEMA US 80018-2022
Transformers in DC Applications:
Design Spec Considerations and Recommendations
Disclaimer
The standards or guidelines presented in a NEMA standards publication are considered technically sound
at the time they are approved for publication. They are not a substitute for a product seller’s or user’s own
judgment with respect to the particular product referenced in the standard or guideline, and NEMA does
not undertake to guarantee the performance of any individual manufacturer’s products by virtue of this
standard or guide. Thus, NEMA expressly disclaims any responsibility for damages arising from the use,
application, or reliance by others on the information contained in these standards or guidelines.
NEMA US 80018-2022
Page 2
© 2022 National Electrical Manufacturers Association
Intro and Scope
Use cases for AC transformers within DC applications are becoming more common with the growth of
renewable generation. For example, project developers might use a medium-voltage DC bus to directly
interconnect solar PV and a battery energy storage system (BESS). Step-up and step-down transformers
are required on both ends of the bus (≈1 kV – 24 kV). Grid planners might also connect a load center
such as small towns/cities with MV DC connections to facilitate greater power flow control and facilitate
renewable penetration. The links are generally in the 24-36 kV range.
In both of the above examples, configurations that involve AC transformers require the use of power
conversion through an inverter or rectifier and may also entail interconnection directly with BESS. For
these use cases, there are special design considerations for the AC transformer to ensure optimal
performance. The purpose of this document is to provide guidance for developers and planners—anyone
charged with specifying the transformer design—to better understand these considerations.
Table
The table below provides a brief overview of the design considerations for AC transformers in various
applications that will be discussed throughout this document.
Design Considerations
Applications
Solar Inverter
BESS
Drive/Rectifier
Voltage Transients
X
Electrostatic Shield
X
Harmonic Currents
X
X
Harmonic Voltages
X
Flux Density
X
X
Grounding
X
X
X
Partial Discharge
X
Voltage Transients and Electrostatic Shielding
One of the unique aspects of medium-voltage AC transformers connected to inverters in battery energy
storage system (BESS) and/or solar photovoltaic applications is that the inverters connected to the low-
voltage side of the transformer can cause fast transient voltages. This happens when the IGBTs of the
inverter are firing to create a sinusoidal waveform (i.e., alternating current or voltage). These transients
can have a dV/dt of 1600 V/µs or higher (2400 V/µs, etc.), with peak voltages of more than seven times
the rated line-ground voltage of the winding. For these applications, we recommend specifying “inverter
duty” insulation, suitable for operation while connected to a pulsed inverter and capable of handling
differential-voltage-to-differential-time (dV/dt) surges. This is not a standard insulation level for a typical
distribution application.
For a solar inverter application, we recommend adding an electrostatic shield between the high-voltage
and low-voltage windings in order to isolate the high-voltage winding from the effect of the fast-rising
voltage on the low-voltage winding. The electrostatic shield acts as an additional dV/dt filter and filters the
voltage gradient of the pulsed inverter output. The electrostatic shield should have single-point grounding
only to avoid circulating current within the shield. See Figure 1.
NEMA US 80018-2022
Page 3
© 2022 National Electrical Manufacturers Association
Figure 1
Schematic of the Transformer and Inverter Winding Appropriate for DC Applications
To validate that the transformer design is able to withstand these transient voltage levels, we recommend
that a lightning impulse test be performed on the transformer design as a type test. We also recommend
that an induced potential test be performed as a routine test on each transformer unit, with an induced
voltage of two times the rated voltage of the transformer.
Harmonic Currents
For a BESS application or a rectifier/drive application, transformer loading is non-sinusoidal. The
customer should specify a harmonic factor (i.e., “K-factor”) for the application as per ANSI/IEEE C57.110.
It is common to specify the transformer with a factor of K-4, which accounts for some overheating caused
by harmonics generated from the inverter.
Harmonic Voltages
For a solar inverter application, the transformer may be subjected to non-linear harmonic voltages, which
cause additional heating in the transformer core and need to be addressed in the design. We recommend
specifying a harmonic voltage factor that corresponds to the harmonic voltage generated by the inverter.
Flux Density
For solar inverter and BESS applications, flux density of the transformer core will vary in operation
depending on the level of active and reactive loads on the transformer. In order to ensure that the
transformer operating flux density does not exceed the saturation flux density of the core steel used in the
transformer, product designers should source appropriate materials such as grain-oriented electric steel
(GOES) or amorphous electrical steel for the transformer core. Saturation of the core would add
additional harmonics to the system along with other negative consequences such as transformer heating
and high noise levels.
To ensure minimum harmonic generation, the saturation flux density of the transformer should be higher
than the maximum flux density reached during normal operation. This maximum flux density is obtained
at the highest secondary voltage, at full capacitive power generation, and at the highest reference
voltage, with minimum continuous frequency.

标签: #设计规范

摘要:

NEMA US 80018-2022《设计规范考虑因素与建议》是面向相关工程设计、合规与项目管理人员的重要参考文件。本文对该标准规范进行系统梳理,概括其适用范围、编制背景、核心设计原则、关键考虑因素与实施建议,重点解析设计流程、风险识别、安全与性能要求、选型安装、验证审查及文档管理等内容。通过条理化的解读,帮助工程师、设计人员、合规负责人和项目管理方快速掌握 NEMA US 80018-2022 的要点,提升标准应用效率,降低设计与合规风险,并为项目规划、设计审查、采购决策和工程实施提供实用参考

展开>> 收起<<
NEMA US 80018-2022 设计规范考虑因素与建议.pdf

共5页,预览3页

还剩页未读, 继续阅读

声明:本文档系会员上传,若文档所含内容侵犯了您的版权或隐私,请立即通知,我们立即给予侵权申诉删除!
作者:小气猫 分类:国际标准 价格:25星币 属性:5 页 大小:180.2KB 格式:PDF 时间:2026-09-27

开通VIP享超值会员特权

  • 多端同步记录
  • 高速下载文档
  • 免费文档工具
  • 分享文档赚钱
  • 每日登录抽奖
  • 优质衍生服务
/ 5
客服
关注