5. Physical and Chemical Properties
5.1 Density—The density of conditioned stabilized insula-
tion in lb/ft
3
(kg/m
3
) shall be determined in accordance with
Section 7.
5.2 Corrosiveness—The loose-fill insulation material shall
be tested for corrosiveness in accordance with Section 8. The
composition of the insulation material shall be such that after
testing, no perforation of the 0.003 in. (0.076 mm) metal
specimens shall be evident when the specimens are observed
over a 40-W appliance light bulb. Notches extending into the
coupon 0.1 in. (3 mm) or less from any edge shall be ignored.
5.3 Critical Radiant Flux—When tested in accordance with
Section 9, the critical radiant flux shall be equal to or greater
than 0.11 Btu/ft
2
·s (0.12 W/cm
2
). All values shall be reported to
two significant digits.
5.4 Fungi Resistance—The loose-fill insulation material
shall be tested and pass fungi resistance as specified in Section
10. All three test specimens shall exhibit growth less than or
equal to the comparative material in order to pass.
5.5 Water Vapor Sorption—Moisture gain in the insulation
shall be no more than 15 % by weight when tested in
accordance with Section 11.
5.6 Odor Emission—Any sample producing a detectable
odor that is classified as objectionable and strong or strong by
more than two panel members shall be considered to have
failed the test when tested in accordance with Section 12.
5.7 Smoldering Combustion—When tested in accordance
with the smoldering combustion test method in Section 13, the
insulation shall show no evidence of flaming and a weight loss
of no greater than 15 % of the specimen weight.
5.8 Thermal Resistance—The standard thermal resistance
values recommended for application shall be expressed in
°F·h·ft
2
/Btu (K·m
2
/W). The R-value shall be measured in
accordance with Section 14. During random sampling, an
average measured R for four specimens that is 95 % of the
labeled value shall be acceptable provided no measurement is
less than 90 % of the labeled value.
3
5.9 Permanency of Flame Retardant Treatment—It is im-
portant to ensure that the fire test response characteristics of the
cellulosic fiber insulation, expressed as the critical radiant flux
in accordance with 5.3 or as the smoldering performance in
accordance with 5.7, not be degraded over time. The rationale
for the concern is that the additives used for improving the fire
test response characteristics of cellulosic fiber insulation are
physically added to the cellulose and are not chemically bound
to the cellulose. Studies have been made in the past indicating
that cellulose insulation treated with boric acid (1),
4
borates
(2), and ammonium sulfate (3) retains its fire test response
characteristics for years, based on cellulose insulation that had
been installed for periods of up to 14 years (4,5). No data has
been presented to the committee to update or revise this
information and no permanency test method has been devel-
oped to date.
5.10 Shrinkage—The shrinkage (S
1
) determined in accor-
dance with Section 7.
5.11 Settling—The settling (S
2
) determined in accordance
with Section 7shall be no greater than 5 %.
6. Workmanship, Finish, and Appearance
6.1 The product shall be free of extraneous foreign materials
such as metals and glass that will adversely affect the perfor-
mance in service.
7. Shrinkage, Settling, and Density
7.1 Density:
7.1.1 Scope—This test method provides a basis for calcu-
lating the product coverage values and for conducting physical
property tests requiring the use of density for specimen
preparation. The shrinkage and settling results provide infor-
mation for installation.
7.1.2 Significance and Use—The density is the weight per
unit volume expected after long-term attic use. All testing of
this product shall be done using specimens having the density
determined by the drop box method described in this section.
7.1.3 Apparatus:
7.1.3.1 Insulation Specimen Container—The drop box ap-
paratus shall consist of an open-top box with sides and bottom
made from
3
⁄
4
-in. (19 mm) thick plywood. The interior of the
box shall be treated with a water sealer. The interior dimen-
sions of the box shall be 22 by 36 by 5-in. (deep) (559 by 914
by 127 mm) for insulation with R < 22 ft
2
·h·°F/Btu (3.87
K·m
2
/W), 22 by 36 by 7
1
⁄
2
-in. (deep) (559 by 914 by 191 mm)
for insulation with 22 < R < 32 ft
2
·h·°F/Btu and 22 by 36 by
10-in. (deep) (550 by 914 by 254 mm) for insulation with R >
32 ft
2
·h·°F/Btu (5.64 K·m
2
/W). A 1.0-in. (25 mm) steel “eye”
shall be attached to each corner to facilitate lifting the box with
a cable or rope harness and pulley system. All box dimensions
shall be within 63 % of the values specified above.
7.1.3.2 Spacer—A 6.0-in. (150 mm) thick spacer shall be
fabricated for positioning the box above a concrete floor. The
spacer shall be fitted with a handle or heavy cord to assist
moving it from below the suspended box. Use a quick release
device to drop the suspended box.
7.1.3.3 Balance—A balance having sufficient capacity to
weigh a specimen container with freshly installed insulation to
within 0.01 lb (5g).
7.1.3.4 Probe and Ruler—A 0.125 60.008 in. (3.2 60.2
mm) diameter metal rod that is pointed on one end shall be
used as a pin gauge. A steel rule with 0.05 in. (1.0 mm) or finer
readability shall be used to determine insulation thicknesses.
The device pictured in Figure 1 of Test Methods C167 is
suitable for use.
7.2 Procedure:
7.2.1 A partially enclosed area is required for specimen
preparation. The enclosure must protect the blowing operation
from wind or strong air currents. Ensure that the geometry of
the room does not influence the stream of insulation from the
3
The ranges of thermal resistance, R, listed in this section are allowed by Federal
Trade Commission 16 CFR Part 460 Trade Regulation Rule: Labeling and
Advertising of Home Insulation.
4
The boldface numbers in parentheses refer to a list of references at the end of
this standard.
C1497 − 24